Chapter 5 Troubleshooting|

Revision August 2008, 2ELE, V1.02

5-3

5.4 Low Voltage (Lv)

Low voltage

Is input power cor rect? O r power cut,
including momentary power loss

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No

No

No

No

Restart after r eset

Check if there i s any malfunction
component i n

power s upply c ircuit

or disconnection

Change defec tiv e component
and chec k c onnection

Check if voltage is
within speci fic ati on

Make nec essary cor rections,
such as change power supply

sy stem for requirement

Check if there i s heavy load
with high s tar t cur rent in the

same power sy stem

Check if Lv occurs when
breaker and magnetic

contactor is O N

Suitable
transformer

power

capacity

Check if voltage between +/B1
and - is greater than

200VDC (for 115V/230V models)
400VDC (for 460V models)

Maybe AC motor drive has m al function.
Please contact DELTA.

Contr ol c ircuit has malfunction or
misoper ation due to noise. P leas e

contact DELTA.