beautypg.com

Delta Electronics AC Motor Drive VFD-EL User Manual

Page 84

background image

Chapter 4 Parameters|

Revision August 2008, 2ELE, V1.02

4-41

40%

50%

60%

For 460V Series

80%

90%

100%

70%

Carrier
Frequency

R

a

te

d

C

u

rr

e

n

t

(%

)

2kHz

4kHz

8kHz

10kHz

12kHz

6kHz

50 with mounting method A

40 with mounting method B

25 with mounting method B

40%

50%

60%

For 115V/230V Series

80%

90%

100%

2kHz

4kHz

8kHz

10kHz

12kHz

6kHz

70%

R

a

te

d

C

u

rr

e

n

t

(%

)

Carrier
Frequency

50 with mounting method A

40 with mounting method B

35 with mounting method A

25 with mounting method B

02.04

Motor Direction Control

Factory Setting: 0

Settings

0

Forward/Reverse operation enabled

1

Reverse

operation

disabled

2

Forward

operation

disabled

This parameter is used to disable one direction of rotation of the AC motor drive direction of

rotation.

02.05

Line Start Lockout

Factory Setting: 1

Settings

0

Disable. Operation status is not changed even if operation
command source Pr.02.01 is changed.

1

Enable. Operation status is not changed even if operation command
source Pr.02.01 is changed.

2

Disable. Operation status will change if operation command source
Pr.02.01 is changed.

3

Enable. Operation status will change if operation command source
Pr.02.01 is changed.

This parameter determines the response of the drive upon power on and operation command

source is changed.

Pr.02.05

Start lockout (Run when power is ON)

Operation status when operation

command source is changed

0

Disable (AC motor drive will run)

Keep previous status

1

Enable (AC motor drive doesn’t run)

Keep previous status

2

Disable (AC motor drive will run)

Change according to the new

operation command source

3

Enable (AC motor drive doesn’t run)

Change according to the new

operation command source