beautypg.com

Delta Electronics AC Motor Drive VFD-EL User Manual

Page 49

background image

Chapter 4 Parameters|

4-6

Revision August 2008, 2ELE, V1.02

Parameter Explanation

Settings

Factory

Setting

Customer

3: Enable. Operation status will change if
operation command source Pr.02.01 is
changed.

0: Decelerate to 0 Hz

1: Coast to stop and display “AErr”

02.06

Loss of ACI Signal
(4-20mA)

2: Continue operation by last frequency
command

1

0: by UP/DOWN Key

1: Based on accel/decel time

2: Constant speed (Pr.02.08)

02.07

Up/Down Mode

3: Pulse input unit (Pr.02.08)

0

02.08

Accel/Decel Rate of
Change of
UP/DOWN
Operation with
Constant Speed

0.01~10.00 Hz

0.01

02.09

Source of Second
Frequency
Command

0: Digital keypad UP/DOWN keys or Multi-
function Inputs UP/DOWN. Last used
frequency saved.
1: 0 to +10V from AVI
2: 4 to 20mA from ACI
3: RS-485 (RJ-45) communication
4: Digital keypad potentiometer

0

02.10

Combination of the
First and Second
Master Frequency
Command

0: First Master Frequency Command
1: First Master Frequency Command+
Second Master Frequency Command
2: First Master Frequency Command -
Second Master Frequency Command

0

02.11

Keypad Frequency
Command

0.00 to 600.0Hz

60.00

02.12

Communication
Frequency
Command

0.00 to 600.0Hz

60.00

0: Save Keypad & Communication
Frequency

1: Save Keypad Frequency only

02.13

The Selections for
Saving Keypad or
Communication
Frequency
Command

2: Save Communication Frequency only

0