beautypg.com

Zone 1: releasing – Potter PFC-6075R User Manual

Page 99

background image

5-93

PFC-6075R • 5403594 • REV D • 9/14

Two Count Releasing Application with Abort Switch
This releasing application requires the activation of two sensors or a manual release input within a designated releasing zone

to start the release sequence. The timing of the release can be affected by the operation of an abort input within the designated

releasing zone.
Activation of an input module classified for the abort switch function will initiate the abort type sequence as selected in

programming. The abort switch must be pressed prior to the pre-discharge timer expires as programmed.

Note: Any device being used to initiate the abort function should be clearly marked and or labeled.

Figure 129. Example of Two Count Releasing Application with Abort Switch

Zone 1: Releasing

1

2

NAC Release

Solenoid

Smoke

Detector

Heat Combo

Abort Switch

Cross Zone Releasing Application with Abort Switch
This releasing application requires the activation of at least one sensor within each of the designated “Cross Zones” or a manual

release within the designated release zone to start the release sequence. The timing of the release can be affected by the operation

of an abort input within the designated releasing zone.
Activation of an input module classified for the abort switch function will initiate the abort type sequence as selected in

programming. The abort switch must be pressed prior to the pre-discharge timer expires as programmed.

Note: Any device being used to initiate the abort function should be clearly marked and or labeled.

Figure 130. Example of Cross Zone Releasing Application with Abort Switch

Zone 1: Alarm

1

Addr Heat

Combo Detector

Zone 2: Alarm

2

Addr Photo

Heat Detector

NAC Release

Solenoid

Zone 3: Releasing

Abort

Switch

Symbol Legend:

= SLC Input

= SLC Output

= Panel Input (I/O)

21