Table 9: Programming Options
Topic
Feature or
Option
Permitted
in UL (Y/N)
Possible Settings
Setting(s) Permitted
in UL864?
Comment
SLC Point
Function
Y
Photo Detector (PSA)
Photo Duct Detector (DSA)
Photo/Heat Detector (PSHA)
Fixed Heat Detector (FHA)
Combination Fixed / ROR Heat
Detector (RHA)
Conv. Zone Module (CIZM)
Mini Contact Mod (MCM)
Single Contact Mod (SCM)
Dual Contact Mod (DCM)
Mon. Output Mod (MOM)
Twin Relay Module (TRM)
Sounder Base (ASB)
Relay Base (ARB)
All settings allowed
Specifies use/type of
SLC device
SLC Point
Dry Contact Input
Functions
Y
Pull Station, Water Flow,
Supervisory, Tamper, Fire Drill,
Trouble Monitor, Aux, Abort,
Reset, Silence, Fire Alarm,
Disable Inputs, Disable Outputs,
Disable Inputs/Outputs, Lamp
Test
All settings allowed
Applies to all dry-
contact input devices
and circuits.
SLC Point
Alarm Verif
Y
Yes/No
All settings allowed
SLC Point
Supervisory
Y
Yes/No
All settings allowed
NACs
Function
Potter/Amseco Sync
Gentex Sync
System Sensor Sync
Wheelock Sync
Constant Output
Resettable Output
Door Holder Output
ANSI Output
City Tie Output
Release / Solenoid Output
All settings allowed
Specifies use of
NAC circuit(s)
Day/Night
Smoke Sensitivity
Y
Full listed range of
smoke detector
All settings allowed
Up to 50 holidays where
day mode is not active.
DACT
Daily Test Call
Y
Any time of day
All settings allowed
Alternates between line
1 and 2 if line 2
is enabled.
E-mail Status
Reports
N
Alarms, Troubles, Supervisory
Test, History & Status Reports
IP-Dialer
IP Based Central
Station Reporting
Y
Alarms, Supervisory,
Trouble & Test Reports
All settings allowed