5-56

PFC-6075R • 5403594 • REV D • 9/14

File New
The File New menu option is used to complete all programming from scratch on the computer. You must select the correct panel

model prior to programming.

Note: It is imperative that you choose the correct panel model prior to programming or completing any data transfers,

otherwise, you cannot complete a successful download to the panel. If this occurs, you will have to reprogram the entire

panel.

Figure 69. Example of File New Dialog Box

File Save / Save As
Once programming has been completed, save your configuration file using either the "File – Save" or "File – Save As" function.

An audit is performed that checks for rule violations; if errors are encountered, you may choose to either save with errors or

cancel the save operation.

Figure 70. Example of Save Panel Dialog Box

Notes:

1. All site specific configuration data is stored in the panel’s non-volatile memory.

2. The next time you make programming changes, you may overwrite the original configuration file with changes. If you

choose to do this, you will lose the original programming report information.

3. The panel configuration file has a .fpcf file extension.

Audit Errors
The Audit Error - Save Anyway? dialog box displays if programming errors are encountered when saving the configuration file.

You may choose to save the file with errors; however, you cannot download the data until all errors are corrected.

Figure 71. Example of the "Save anyway?" Dialog Box