beautypg.com

Main board wiring specifications – Potter PFC-6075R User Manual

Page 12

background image

2-6

PFC-6075R • 5403594 • REV D • 9/14

Main Board Wiring Specifications

There are several wiring requirements to consider before connecting circuits to the main board: (1) the circuit separation,

and (2) wiring types.

Circuit Separation
Proper separation between the different types of circuits must be maintained between Power Limited, Non-Power Limited, and

High Voltage wiring to reduce electrical interferences, transient voltage or voltage ratings.

y

y

Separations between the different wiring types must be maintained by at least ¼ inch and the wire insulation must be for the

higher voltage.

y

y

The control panel cabinet has sufficient knockouts located around the periphery allowing the installer to maintain separation

between power limited and non-power limited connections.

Wiring Types
Wiring specifications must be followed to prevent damage or other consequences.

Refer to table below for a breakout of the different wiring requirements shown by circuit type:

Table 5: Main Board Circuit Wiring Types

Wiring Type

Type of Circuit

Voltage

Power

AC Connection

High Voltage

Non-Power Limited

Battery Connection

Low Voltage

Non-Power Limited

Trouble Relay

Low Voltage

Non-Power Limited

Supervisory Relay

Low Voltage

Non-Power Limited

Alarm Relay

Low Voltage

Non-Power Limited

I/O Circuits

Low Voltage

Power Limited

Notification Device Circuits (NACs)

Low Voltage

Power Limited

P-Link RS-485 Connections

Low Voltage

Power Limited

Signaling Line Circuit

Low Voltage

Power Limited

Phone Line – DACT

High Voltage

Non-Power Limited