Main board wiring specifications – Potter PFC-6075R User Manual
Page 12
2-6
PFC-6075R • 5403594 • REV D • 9/14
Main Board Wiring Specifications
There are several wiring requirements to consider before connecting circuits to the main board: (1) the circuit separation,
and (2) wiring types.
Circuit Separation
Proper separation between the different types of circuits must be maintained between Power Limited, Non-Power Limited, and
High Voltage wiring to reduce electrical interferences, transient voltage or voltage ratings.
y
y
Separations between the different wiring types must be maintained by at least ¼ inch and the wire insulation must be for the
higher voltage.
y
y
The control panel cabinet has sufficient knockouts located around the periphery allowing the installer to maintain separation
between power limited and non-power limited connections.
Wiring Types
Wiring specifications must be followed to prevent damage or other consequences.
Refer to table below for a breakout of the different wiring requirements shown by circuit type:
Table 5: Main Board Circuit Wiring Types
Wiring Type
Type of Circuit
Voltage
Power
AC Connection
High Voltage
Non-Power Limited
Battery Connection
Low Voltage
Non-Power Limited
Trouble Relay
Low Voltage
Non-Power Limited
Supervisory Relay
Low Voltage
Non-Power Limited
Alarm Relay
Low Voltage
Non-Power Limited
I/O Circuits
Low Voltage
Power Limited
Notification Device Circuits (NACs)
Low Voltage
Power Limited
P-Link RS-485 Connections
Low Voltage
Power Limited
Signaling Line Circuit
Low Voltage
Power Limited
Phone Line – DACT
High Voltage
Non-Power Limited