5-94
PFC-6075R • 5403594 • REV D • 9/14
Programming Modules
This section addresses how to program optional all P-Link appliances, including the DACT (UD-1000), RA-6500R, RA-6075R,
CA-6075 Class A expansion card, LED-16 annunciators, and others.
CA-6075 Class A Converter Module
The PFC-6075R supports one (1) Class A Expander card.
To add and configure a Class A module:
1. Select the Class A Card function from the system panel.
2. Click the Add Device button. The “Add Device” window displays.
Figure 131. CA-6075 Class A – Add Device Window
Note: If you attempt to add more than one (1) Class A card, an error dialog box displays, as shown below:
Figure 132. Unable to Add Dialog Box
3. Double-click in the “SLC Class” field to select class type (A or B).
4. Double-click in the “P-Link Class” field to select class type (A or B).