beautypg.com

Notification appliance circuits installation – Potter PFC-6075R User Manual

Page 30

background image

3-24

PFC-6075R • 5403594 • REV D • 9/14

Notification Appliance Circuits Installation

There are two (2) NAC circuits provided on the PFC-6075R rated as continuous 3 amps at 24 VDC. The NAC circuits may be

configured for Class A or Class B. (Please refer to the Class A and B wiring examples located in this section.)

NAC Wiring

y

y

Outputs are supervised and regulated.

y

y

Circuits are power limited.

y

y

Type of NAC output is selectable, and may be configured for strobe synchronization with Potter/AMSECO, Cooper

Wheelock®, Gentex®, or System Sensor® strobe devices. Refer to the listing of compatible models located in the

“NAC Compatibility Document”, Potter #5403592, for this information.

y

y

The CA-6075 Class-A Expander may be programmed to allow for operation of the NACs. The expander adheres to the

same circuit rating, supervision and regulation as other circuits.

NAC Maximum Wiring Impedance Formula
The maximum impedance is a function of the load placed on the circuit. To calculate the maximum line current impedance, use

the following formula:
(Alarm Current of Notification Appliances) x (Wire Resistance) < 3 Volts

NAC Wiring Configurations
Examples of Class B and Class A Wiring follow.

Figure 24. NAC

Class

B

Wiring

Example

NAC 1 NAC 2

-

+ -

+

5.1k EOL

Potter Part #3005013

Notification

Appliance

Notes:

1. The Potter part number for the listed end of line assembly is #3005013 EOL Resistor Assembly.

2. The panel has ground fault detection on the NAC circuits. The impedance to ground for ground fault detection is 0 ohms.

DWG #602-4A