Appendix F: TroubleShooting Tips
This section provides basic error messages, their descriptions and recommended actions for each condition.
Table 28: Troubleshooting
Error Message
Error Description/Action
Keypad “##”: Missing
The panel is not able to communicate with the annunciator.
Action: Check wiring and programming.
SLC “##”: TYPE ERR
Device is not programmed for the correct function.
Action: Program device for correct function.
SLC “##”: XTRA DEV
FACP found a non-programmed device.
Action: Run LEARN or program specific device.
SLC “##”: DUP ADDR
FACP found multiple devices with the same address.
Action: Manually reassign address of one of the devices.
SLC LOOP SHORTED
There is a short on the SLC loop wiring.
Action: Locate short and repair accordingly.
NAC “##”: OPEN
There is an open on the wiring.
Action: Locate open and repair accordingly.
NAC “##”: Shorted
There is a short on the Notification Circuit’s wiring.
Action: Locate short and repair accordingly.
SLC 1: Missing
The panel is not able to communicate with a device.
Action: Check device is currently operating and/or connect device to SLC loop.
SLC “##”: OPEN/PWR
•y
Monitored Output Module is missing 24 VDC connection.
Action: Check for 24 VDC to the device.
•y
Back up batteries are missing or need to be replaced.
Action: Connect or replace batteries as needed.