beautypg.com

Fire communications bridge installation (fcb-1000) – Potter PFC-6075R User Manual

Page 43

background image

3-37

PFC-6075R • 5403594 • REV D • 9/14

Setting Addresses
The RLY-5's address is set by dip switch S1, which is located on the back of the board. The address must be set in the range of

one to thirty-one (1–31) to be recognized by the panel. (Refer to the "P-Link Addresses" table shown earlier in this section for

DIP switch programming.)

Figure 45. Relay Board Back Panel View Showing Dip Switch Location

Fire Communications Bridge Installation (FCB-1000)

This panel supports one (1) Fire Communications Bridge accessory. This module provides an optional remote IP connection for

IP reporting functionality. The FCB-1000 is controlled over the 4-wire P-Link connection. This then can be mounted inside the

AE-8 or AE-14 accessory cabinets, or the optional rack-mount kit (FCB-1000RM). The FCB-1000RM includes a standard 19

inch rack-mount enclosure, which can then be installed directly into the IT equipment rack.

Note: The Ethernet IP connection is limited to same room installation. This connection shall be limited to 20 feet and enclosed in

conduit or equivalently protected against mechanical injury.

Figure 46. FCB-1000 Board & FCB-1000RM Showing Rack Mount

Figure 47. FCB-1000 Wiring to Control Panel Example

DWG #608-13

DWG #608-14

DWG #608-21

Dip Switches

P-Link

Connections

S1

DWG #608-26

P-Link

-

+ A B

P-Link from

control panel

Example:

Powered by

control panel