Fire panel operating instructions – Potter PFC-6075R User Manual

Page 133

background image

Normal Standby

The green AC POWER LED will be illuminated and the user defined message on the LCD will be displayed. If

the AC power is removed for more than 5 seconds, the green AC power LED will extinguish.

Acknowledging

Off normal events are acknowledged by pressing the ACK key while reviewing events. After all events have been

acknowledged, the buzzer will deactivate and the associated LED will stop flashing and remain on continuously.

During Positive Alarm Sequence operation the “ACK” key must be pressed within 15 seconds of the alarm

initiation to activate the investigation timer.

Alarm Condition

The red ALARM LED will be illuminated anytime an alarm is occurring in the system. The LCD will display the

number of inputs in alarm, and the buzzer will be activated. The buzzer will remain active until all alarms have

been acknowledged, or until the Silence key is pressed.

Silencing Alarm

When the system is in Alarm, the notification circuits (strobes and horns) can be shut off by pushing the SILENCE

button.

Resetting Alarm

After the condition that caused the alarm has been identified and corrected, the system may be reset to the Normal

Standby by pressing the RESET button.

Supervisory Condition

When a supervisory condition is detected, the amber SUPERVISORY LED will illuminate and the buzzer will

sound. The LCD display will indicate the number of supervisory events that are active. The local buzzer will

sound until all supervisory events have been acknowledged.

Restoring Supervisory

Condition

If the Supervisory condition is non-latching, once the device is restored to the normal condition, the supervisory

event will clear. If the supervisory condition is latching, the device that was activated must be restored and the

RESET pressed.

Trouble Condition

When a fault condition occurs, the amber TROUBLE LED will illuminate and the local buzzer will sound

until the fault is removed or the ACK button is pressed acknowledging the trouble condition. If the buzzer is

acknowledged and the fault is not removed within 24 hours, the buzzer will resound.

Silencing Trouble(s)

When a trouble is occurring, the local buzzer will sound until either all troubles have been acknowledged or the

SILENCE button is pressed.

Ground Fault

When a conductor contacts and earth ground, the amber EARTH FAULT LED will illuminate and the LCD

display will provide further information of where the fault is located.

Pre-Release

(Releasing Panels Only)

The amber Pre-Release LED will illuminate when the system is in a count down timer for an agent release.

Additionally, pre-release events and countdown timers are displayed on the LCD.

Release

(Releasing Panels Only)

The red Release LED will illuminate when a release condition is active. Additionally, release events will be

displayed on the LCD.

Agent Release Abort

(Releasing Panels Only)

If the system is being used as an agent releasing panel and a pre-discharge timer is programmed, the release may be

aborted by pressing the abort switch. For ULI installations, pushing the Abort will allow the timer to countdown

until 10 seconds and then halt. Releasing and reactivating the Abort will set the timer to 10 seconds.

Testing and

Maintenance

Test this system monthly or more frequently as required by the AHJ. Before conducting any testing contact

the building personnel and the monitoring facility as applicable. When testing a system configured for

releasing, activate the releasing disconnect switch to prevent accidental discharge of a suppression system.

Test the circuits as outlined in the Installation Manual. Test in accordance with NFPA 72 Inspection, Testing

and Maintenance Chapter(s) and any local requirements. The batteries should be marked with the date of

installation and replaced every four years or sooner if battery trouble occurs. Batteries should be checked with

a tester acceptable to the AHJ such as a Stone Technologies model STC612A or equivalent. In case of a fuse

replacement, refer to the Installation Manual for the proper rating. Contact the agency below for service or

operational questions.

Fire Panel Operating Instructions

For service, contact:

Name:
Company:
Address:
Telephone:

5409071–Rev B