Potter PFC-6075R User Manual
Page 78
5-72
PFC-6075R • 5403594 • REV D • 9/14
3. In the “Subject” field, enter one or more of the following keywords:
• History to send a current event history report back to sender.
• Status to send a current detector (sensitivity) status report back to sender.
• Configuration to send a current configuration file back to sender.
• Unsubscribe to stop the current e-mail settings for the sender until panel is reset or that e-mail address sends a
“Subscribe” to the panel.
• Subscribe to activate e-mail settings for the sender.
Note: Keywords are NOT case sensitive and more than one can be entered in the subject line of the e-mail.
4. There are no restrictions on contents entered into the body of the e-mail.
Important Reminders!
• The person sending the e-mail must be added to the e-mail list in the “E-mail Reporting” section of the software as
shown below. If the sender is not in the list, the panel will not respond.
• The “Enable E-mail Requests” option must also be checked for the sender to receive e-mails when requested from the
panel or a remote PC.
Figure 95. E-mail Reporting Window
System e-mail communications and functions are intended for informational reporting purposes only. They are intended to be used as a
convenience function. E-mail communications should NOT be used as a primary means of reporting emergency information.
Note: You may choose not to select
specific event types or reports for
e-mail addressees.
If so, choose Browse List from
the Data Transfer panel menu
option. Then scroll through e-mail
addresses and select one or more
recipients.
Sender's e-mail must be in the
e-mail list and the Enable E-mail
Requests box must be checked.