Potter PFC-6075R User Manual
Page 54
5-48
PFC-6075R • 5403594 • REV D • 9/14
Table 9: Programming Options
Topic
Feature or
Option
Permitted
in UL (Y/N)
Possible Settings
Setting(s) Permitted
in UL864?
Comment
Zone
Zone Type
Y
Alarm
Supervisory
Positive Alarm Sequence
Auxiliary
Releasing
Fire Drill
System Alarm
System Supervisory
System Trouble
All settings allowed
Zone
Alarm Count
Y
1-10
All settings allowed
Zone
Silenceable
Y
Yes/No
All settings allowed
Zone
Silence Inhibit
Y
Yes/No
All settings allowed
Zone
Auto Silence
Y
Yes/No
All settings allowed
Zone
Auto Unsilence
Y
Yes/No
All settings allowed
Zone
Restore Delay
Y
0-300 Sec
Full range allowed
Zone
Latching
Y
Yes/No
All settings allowed
Zone
Local
Y
Yes/No
All settings allowed
Zone
Output Pattern
Y
Constant
ANSI Temporal
March Code
Double Time
All settings allowed
Zone
Day Sensitivity
Y
1.1%-3.5%
Full range allowed
Within listed range
of sensor
Zone
Night Sensitivity
Y
1.1%-3.5%
Full range allowed
Within listed range
of sensor
Zone
Fixed Heat
Setting
Y
135
̊
F-185
̊
F
Full range allowed
Within listed range
of sensor
Zone
Combo ROR/
Fixed Setting
Y
135
̊
F-174
̊
F
All settings allowed
Within listed range
of sensor
Releasing
Abort Type
Y
ULI, IRI, AHJ, NYC
ULI
Only ULI is permitted in
UL installations
Releasing
Pre-Release
Timer
Y
0-60 Sec
Full range allowed
Length of time of
pre-release
Releasing
Pre-Release
Pattern
Y
Constant
ANSI Temporal
March Code
Double Time
All settings allowed
Pattern from NAC
during Pre-Release
Releasing
Manual Release
Timer
Y
0-30 Sec
Full range allowed
Length of time of
Pre-Release
Releasing
Manual Release
Abort Allowed
Y
Yes/No
All settings allowed
Specifies whether Man-
Release is Cancellable
Releasing
Soak Time
Y
0-20 Minutes
Full range allowed
Length of time the
release circuit is active
post release