PSN-1000/PSN-1000(E) Battery Calculation Worksheet

Complete one for all P-Link devices powered by the PSN-1000 / PSN-1000(E)

Device Type

Qty

Standby

(mA)

Total

Standby

(mA)

Alarm

(mA)

Total

Alarm

(mA)

PSN-1000 / PSN-1000(E) Main Board

1

60

200

200

LCD Remote RA-6075R / RA-6075

20

25

LCD Remote RA-6500R / RA-6500

20

50

PSN-1000/E Power Expander

15

15

LED-16 P-Link

LED-Current (if applicable, see Note 6)

25

15

25

210

DRV-50

LED-Current (if applicable, see Note 6)

25

10

25

215

RLY-5

Relay Current (if applicable, see Note 6)

25

10

35

135

FCB-1000

25

25

FIB-1000

30

30

SPG-1000

40

40

NAC 1
NAC 2
NAC 3
NAC 4
NAC 5
NAC 6
SLC Current Draw

Total (ma)

Total (ma)

Convert to Amps

x 0.001

Convert to Amps

x 0.001

(*Refer to maximum allowable standby current) Total A:

Total A:

Multiply by standby hours

x____

60 minutes per hour

Alarm time (minutes)

Example:

5 minute alarm: enter 12

10 minute alarm: enter 6

÷

____

Total Standby AH

Total Alarm AH

+Total Standby AH

Total AH

Efficiency Factor

÷

0.85

Required AH

*Maximum Allowable Standby Current

(UL 24-Hour Standby Time)

7 AH

.230 A

18 AH .619 A

33 AH 1.151 A

55 AH 1.930 A

Important Notes:

1) The PSN-1000/E enclosure can house up to two (2) 18 AH batteries. Larger

batteries require accessory enclosure, part #SSU00500.

2) NFPA 72 requires 24 hours of standby power followed by 5 minutes alarm

activation.

3) NFPA 12, 12A requires 24 hours and five minutes of alarm activation.

4) Door holder circuits configured to disconnect upon AC loss need not be included

in the battery standby calculation since they will not draw power during that

time. Door holders will contribute to standby current draw when AC is present.

5) Total current must not exceed power supply rating (10A).

6) LED/Relay current must be accounted for in the battery calculation for the

supplying source.