PSN-1000/PSN-1000(E) Battery Calculation Worksheet
Complete one for all P-Link devices powered by the PSN-1000 / PSN-1000(E)
Device Type
Qty
Standby
(mA)
Total
Standby
(mA)
Alarm
(mA)
Total
Alarm
(mA)
PSN-1000 / PSN-1000(E) Main Board
1
60
200
200
LCD Remote RA-6075R / RA-6075
20
25
LCD Remote RA-6500R / RA-6500
20
50
PSN-1000/E Power Expander
15
15
LED-16 P-Link
LED-Current (if applicable, see Note 6)
25
15
25
210
DRV-50
LED-Current (if applicable, see Note 6)
25
10
25
215
RLY-5
Relay Current (if applicable, see Note 6)
25
10
35
135
FCB-1000
25
25
FIB-1000
30
30
SPG-1000
40
40
NAC 1
NAC 2
NAC 3
NAC 4
NAC 5
NAC 6
SLC Current Draw
Total (ma)
Total (ma)
Convert to Amps
x 0.001
Convert to Amps
x 0.001
(*Refer to maximum allowable standby current) Total A:
Total A:
Multiply by standby hours
x____
60 minutes per hour
Alarm time (minutes)
Example:
5 minute alarm: enter 12
10 minute alarm: enter 6
÷
____
Total Standby AH
Total Alarm AH
+Total Standby AH
Total AH
Efficiency Factor
÷
0.85
Required AH
*Maximum Allowable Standby Current
(UL 24-Hour Standby Time)
7 AH
.230 A
18 AH .619 A
33 AH 1.151 A
55 AH 1.930 A
Important Notes:
1) The PSN-1000/E enclosure can house up to two (2) 18 AH batteries. Larger
batteries require accessory enclosure, part #SSU00500.
2) NFPA 72 requires 24 hours of standby power followed by 5 minutes alarm
activation.
3) NFPA 12, 12A requires 24 hours and five minutes of alarm activation.
4) Door holder circuits configured to disconnect upon AC loss need not be included
in the battery standby calculation since they will not draw power during that
time. Door holders will contribute to standby current draw when AC is present.
5) Total current must not exceed power supply rating (10A).
6) LED/Relay current must be accounted for in the battery calculation for the
supplying source.