EVCO c-pro kilo AHU User Manual
Page 86

C-PRO KILO AHU APPLICATION MANUAL
Pag. 86
1293
Status_AirExtShutter
0
0
6
0=Disabilitato,
1=OFF,
2=Opening,
3=ON,
4=Closing,
5=ALL,
6=Allineamento
R/W
1294
Position_AirShutter
0.00
0.00
100.00
0% -100.00%
R/W
1537
PT01_Start_NightTB ( Low )
0
0
86399
R/W
1538
PT01_Start_NightTB ( High )
1539
PT02_End_NightTB ( Low )
0
0
86399
R/W
1540
PT02_End_NightTB ( High )
1541
PT03_OffsetSetPoint_Night
0.0
-20.0
68.0
R/W
1542
MOdE_SummerWinterMode
1
0
1
0=Estate
(Cooling),
1=Inverno
(Heating)
R/W
1543
SEtC_SummerSetPoint
24.0
-15.0
158.0
R/W
1544
SEtH_WinterSetPoint
20.0
-15.0
158.0
Winter Set Point
or Set Point
unique(if selected
by PH27)
R/W
1545
PU01_Humidifier_SetPoint
55
0
100
R/W
1546
OS01_OffsetSetPoint_DI
0.0
-20.0
68.0
R/W
1547
OS02_OffsetSetPoint_SUP
0.0
-20.0
68.0
R/W
1548
PM00_Limit_HourFan ( Low )
20000
0
100000
ore x 10
R/W
1549
PM00_Limit_HourFan ( High )
1550
PM01_SupplyFan_Hours ( Low )
0
0
100000
R/W
1551
PM01_SupplyFan_Hours ( High )
1552
PM02_ReturnFan_Hours ( Low )
0
0
100000
R/W
1553
PM02_ReturnFan_Hours ( High )
1554
PM10_Limit_HourPump ( Low )
20000
0
100000
ore x 10
R/W
1555
PM10_Limit_HourPump ( High )
1556
PM11_Pump_Hours ( Low )
0
0
100000
R/W
1557
PM11_Pump_Hours ( High )
1558
PM20_EnManual_SupplyFan
0
0
1
R/W
1559
PM21_ForceSuppyFan
0.00
0.00
100.00
R/W
1560
PM23_EnManual_ReturnFan
0
0
1
R/W
1561
PM24_ForceReturnFan
0.00
0.00
100.00
R/W