EVCO c-pro kilo AHU User Manual
Page 49
C-PRO KILO AHU APPLICATION MANUAL
Pag. 49
6.2.6 Unit with 3 coils with dehumidification (PG00=6)
The MOdE parameter with default setting on WINTER.
This unit provides utilization of the expansion (PG02=1).
The regulation of the two fans starts while set on default on the inverter with On/Off
(PF01=3).
The number of coils configured is PG01=3; the post-heating is guaranteed by the third coil.
The dehumidification is enabled PG12=1.
The regulation of the shutter is enabled for free-cooling/free-heating (PG07=1, PS01=1).
The recuperator utilized is that which is at cross flow PG13=1.
PIN
ANALOGUE INPUTS
AI1
Ambient air temperature probe (NTC)
AI2
Delivery air temperature probe (NTC)
AI3
External air temperature (NTC)
AI4
Ambient humidity probe (4..20 mA)
AI5
Expulsion air temperature probe (NTC)
AI6
Anti-freeze temperature probe (NTC)
AI7
Not utilized
AI8
Preheating air temperature probe (NTC)
AI9
Air quality probe CO2/VOC (4..20 mA)
AI10
External humidity probe (4..20 mA)
PIN
DIGITAL INPUTS
DI1
On/Off remote
DI2
Summer/winter remote commutation
DI3
Thermal delivery fans
DI4
Dirty pressure switch recuperator
DI5
Pressure switch air filter
DI6
Airflow meter
DI7
Thermal pickup fan
DI8
Humidifier alarm
DI9
Inverter delivery fan alarm
DI10
Inverter pickup fan alarm
DI11
Heating pump alarm
DI12
Cooling pump alarm
DI13
Fire/smoke alarm
DI14
Not utilized
PIN
ANALOGUE OUTPUTS
AO 1
Not utilized
AO 2
Heating valve command (0-10V)
AO 3
Dehumidification and cooling valve command (0-10V)
AO 4
Not utilized
AO 5
Fans inverter command (0-10V)
AO 6
Post-heating valve command (0-10V)
PIN
DIGITAL OUTPUTS