EVCO c-pro kilo AHU User Manual
Page 34
C-PRO KILO AHU APPLICATION MANUAL
Pag. 34
PS09
Minimum variation regulation for operating the
external air shutters
0.0
0.0
90.0
%
IS-SE
Enabled if
PS09>0
PS10
Fixed value for opening external air shutters
50.0
0.0
100.0
%
IS-SE
Only with
fixed
regulation
(PG07=2)
PS11
Offset at Set Point during winter (at ambient
temp.) until the external air shutters remain
closed during winter operating mode
2.0
0.0
30.0
°C
IS-SE
Only with
regulation
module
(PS01=1)
PS12
Differential enabling free-cooling and free-
heating in temperature
2.0
0.0
20.0
°C
IS-SE
PS13
Differential Set Point enabling free-cooling and
free-heating in temperature
4.0
0.0
20.0
°C
IS-SE
PS15
Differential enabling free-cooling and free-
heating heat exchanger
8.0
1.0
100.0
KJ/
Kg
IS-SE
PS16
Differential Set Point enabling free-cooling and
free-heating heat exchanger
10.0
1.0
200.0
KJ/
Kg
IS-SE
PS20
Set Point – Air Quality Control
600
0
10000
ppm
IS-SE
PS21
Differential – Air Quality Control
100
0
2000
ppm
IS-SE
RECUPERATORS
Menu accessible only if PG13>0
Pr01
Differential Set Point for regulation of
recuperator
5.0
0.0
20.0
°C
IS-RH
Pr02
Differential of regulation of recuperator
3.0
0.0
20.0
°C
IS-RH
Pr03
Minimum Set Point expulsion temperature
1.0
PH03
PH04
°C
IS-RH
Pr04
Differential minimum expulsion temperature
4.0
0.0
20.0
°C
IS-RH
Pr05
By pass cycle time of recuperators at cross flow
for melting
5
1
99
Min
IS-RH
Pr07
Minimum velocity of rotating heat recuperator
velocity
0.0
0.0
Pr08
%
IS-RH
Pr08
Maximum velocity of rotating heat recuperator
velocity
100.0
Pr07
100.0
%
IS-RH
Only if
PG13=4
PUMPS
Menu accessibile only if PG10=1 or PG11=1
PP01
Types of pump regulation
0: Continuous regulation
1: Regulation On/Off
0
0
1
-
IS-P
PP02
Set Point on the regulation ramp for pump
startup
5.0
PP03
90.0
%
IS-P
PP03
Set Point on the regulation ramp for pump
shutdown
2.0
1.0
PP02
%
IS-P
Only if
PP01=1
PP04
Wait time for pump shutdown (only with
PP01=1)
10
1
99
Min
IS-P
OFF – Unit
immediately
shuts down
pump
HUMIDIFIER
This menu is accessible only if PG06=1
PU02
Type of regulation for humidifier
0: ON/OFF Regulation
1: Module Regulation
0
0
1
-
IS-U
PU03
Differential for the regulation of the humidifier
10
0
100
%
IS-U
PU10
Enable humidifier control with temperature of
delivery
YES (1)
NO (0)
YES (1)
-
IS-U
PU11
Set Point at temperature of delivery enabling
humidifier
22.0
PH03
PH04
°C
IS-U
Only if
PU10=1
PU12
Differential on the temperature of delivery to
enable humidifier
3.0
0.0
20.0
°C
IS-U
Only if
PU10=1
ALARM PARAMETERS