EVCO c-pro kilo AHU User Manual
Page 18
C-PRO KILO AHU APPLICATION MANUAL
Pag. 18
Conn.
Label
Description
JA-1
AI1
Analogue input n.1 (for NTC probe)
JA-2
AI2
Analogue input n.2 (for NTC probe)
JA-3
AI3
Analogue input n.3 (for NTC probe)
JA-4
AI4
Analogue input n.4 (for NTC probe / transducers 0-20 mA /
transducers 4-20 mA); ratiometric transducers 0-5 V upon
request
JA-5
AI5
Analogue input n.5 (for NTC probe / transducers 0-20 mA /
transducers 4-20 mA); ratiometric transducers 0-5 V upon
request
JA-6
GND
Common analogue inputs
JA-7
+5V
Supplying power to ratiometric transducers
JA-8
+12V
Supplying current to transducers
JB
Connector for the digital signals
Conn.
Label
Description
JB-1
ID1
Digital input n.1
JB-2
ID2
Digital input n.2
JB-3
ID3
Digital input n.3
JB-4
ID4
Digital input n.4
JB-5
ID5
Digital input n.5
JB-6
ID6
Digital input n.6
JB-7
ID7
Digital input n.7
JB-8
GND
Common digital inputs
JD:
Connector for cut-phase output EVDFAN1 (analogue output 1)
Conn.
Label
Description
JD-1
VDC
Supplying power to cut-phase module EVDFAN1
JD-2
AO1
Cut-phase module output EVDFAN1
In order to utilize the cut-phase module EVDFAN1, it is necessary to supply the expansion
with an alternate current; the phase which supplies power to the controller must be the same
as that which is supplied to both the expansion and the module.
JE:
Connector for the analogue outputs 2 and 3 (for isolation); upon request, not available in
daytime models
Conn.
Label
Description (Version V+I)
JE-1
AO2
0-10VDC
JE-2
GND
Common analogue outputs
JE-3
AO3
4-20mA
Description (Versione I+I)
JE-1
AO2
4-20 mA
JE-2
GND
Common analogue outputs
JE-3
AO3
4-20 mA
Description (Versione V+V)
JE-1
AO2
0-10VDC
JE-2
GND
Common analogue outputs
JE-3
AO3
0-10VDC