2 unit in summer operating mode (pg00=2) – EVCO c-pro kilo AHU User Manual
Page 44
C-PRO KILO AHU APPLICATION MANUAL
Pag. 44
6.2.2 Unit in SUMMER operating mode (PG00=2)
The MOdE parameter can be setup by default in ESTATE (SUMMER).
Unit at single coil PG01=1.
The fan regulations can be set up by default in On/Off (PF01=1).
The primary regulation can be set up by default on the valve (PG04=1).
The regulation of the shutter is fixed (PG07=2).
PIN
ANALOGUE INPUTS
AI1
Ambient air temperature probes (NTC)
AI2
Air delivery temperature probes (NTC)
AI3
Not utilized
AI4
Not utilized
AI5
Not utilized
PIN
DIGITAL INPUTS
DI1
On/Off remote
DI2
Not utilized
DI3
Thermal delivery fan
DI4
Air filter pressure switch
DI5
Anti-freeze alarms
DI6
Air flow status
DI7
Not utilized
PIN
ANALOGUE OUTPUTS
AO 1
Not utilized
AO 2
Cooling valve control (0-10V)
AO 3
Not utilized
PIN
DIGITAL OUTPUTS
DO1
Delivery fan
DO2
Pickup fan
DO3
Not utilized
DO4
Opening external air shutters
DO5
Closing external air shutters
DO6
Dirty filter indicator
DO7
Alarm
RTC system clock present.