1 directory of configuration parameters – EVCO c-pro kilo AHU User Manual
Page 31

C-PRO KILO AHU APPLICATION MANUAL
Pag. 31
5.1
Directory of configuration parameters
 
Code 
 
Description parameter
Default
Min
Max
UM
Menu
Note
CLOCK MENU
This menu is accessible only if PG03=1
PT01
Begin nocturnal operating mode
00:00:00
00:00:00
23:59:59
-
OR
PT02
End nocturnal operating mode
00:00:00
00:00:00
23:59:59
-
OR
PT03
Offset of Set Point nocturnal operating mode
0.0
-20.0
20.0
°C
OR
Level
1
USER MENU
MOd
E 
Operating mode 
0: Summer (Cooling) 
1: Winter (Heating) 
1
0
1
-
UT
SEtC
Set Point summer
24.0
PH03
PH04
°C
SEtH
Set Point winter/single
20.0
PH03
PH04
°C
UT
If PH27=1 
(single Set 
Point), the 
single Set 
Point utilized 
for regulation 
and SEtH. 
PU01
Set Point for humidity management
55
0
100
%
UT
OS01
Offset at regulation Set Point from digital input
0.0
-20.0
20.0
°C
UT
If PH25=1
OS02
Offset at regulation Set Point from Supervisor
0.0
-20.0
20.0
°C
UT
If PH26=1
PSd1
Password for User Level (1)
0
-999
9999
-
UT
Level
2
MAINTENANCE OPERATOR MENU
PM00
Limit the maximum hours of fan operation. 
Related alarms will sound if maximum hours are 
exceeded. 
20000
0
100000
Hrs.
MA-F
PM01
Hours of fan operation - delivery
0
0
100000
Hrs.
MA-F
PM02
Hours of fan operation - pickup
0
0
100000
Hrs.
MA-F
PM10
Limit the maximum hours of pump operation. 
Related alarms will sound if maximum hours are 
exceeded. 
20000
0
100000
Hrs.
MA-F
PM11
Hours of cooling pump operation
0
0
100000
Hrs.
MA-F
PM12
Hours of heating pump operation
0
0
100000
Hrs.
MA-F
PM90
Last date of machine maintenance
-
MA-F
PM20
Manual/automatic fan operation - delivery 
0: Auto – automatic operation 
1: Manu – manual operation 
0 (Auto)
0 (Auto)
1 (Manu)
-
MA-M
PM21
Force the value of the fan in manual operation
0.0
0
100.0
%
MA-M
If fan On/Off 
set PM21>0 to 
activate 
PM23
Manual/automatic fan operation - pickup 
0: Auto –automatic operation 
1: Manu –manual operation 
0 (Auto)
0 (Auto)
1 (Manu)
-
MA-M
PM24
Force the value of the fan pickup module in 
manual operation 
0.0
0
100.0
%
MA-M
If fan On/Off 
set PM24>0 to 
activate 
PM26
Manual/automatic humidifier operation 
0: Auto –automatic operation 
1: Manu –manual operation 
0 (Auto)
0 (Auto)
1 (Manu)
-
MA-M
PM27
Force the value of the humidifier in manual 
operation 
0
0
100
%
MA-M
If humidifier 
On/Off set 
PM27>0 to 
