C-PRO KILO AHU APPLICATION MANUAL
Pag. 46
6.2.4 Unit for operation in WINTER/SUMMER with humidity
and recuperation (PG00=4)
The MOdE parameter starts while set on default on WINTER
Unit at single coil PG01=1.
The regulation of the fans starts while set on default on inverter with On/Off (PF01=3).
The primary regulation starts while set on default on the valve (PG04=1).
The regulation of the shutter is enabled for free-cooling/free-heating (PG07=1, PS01=1).
The recuperator in use is that at cross flow PG13=1.
PIN
ANALOGUE INPUTS
AI1
Ambient air temperature probe (NTC)
AI2
Air delivery temperature probe (NTC)
AI3
External air temperature (NTC)
AI4
Ambient humidity probe (4..20 mA)
AI5
Expulsion air temperature probe (NTC)
PIN
DIGITAL INPUTS
DI1
On/Off remote
DI2
Summer/winter remote commutation
DI3
Thermal delivery fan
DI4
Pressure switch recuperator dirty
DI5
Anti-freeze thermostat
DI6
Humidifier alarm
DI7
Thermal pickup fans
PIN
ANALOGUE OUTPUTS
AO 1
Not utilized
AO 2
Valve command heating/cooling (0-10V)
AO 3
Fans inverter command (0-10V)
PIN
DIGITAL OUTPUTS
DO1
Delivery fans
DO2
Pickup fans
DO3
Shutter by-pass recuperator
DO4
Opening of external air shutter
DO5
Closing of external air shutter
DO6
Humidifier on/off
DO7
Alarm
RTC system clock present.