4 free-cooling and free-heating regulation – EVCO c-pro kilo AHU User Manual
Page 68

C-PRO KILO AHU APPLICATION MANUAL
Pag. 68
6.11.4 Free-Cooling and Free-Heating Regulation
The regulation of the free-cooling/free-heating commands the opening of the external air 
shutter. When free-cooling/free-heating conditions exist; or if the regulation can be enabled 
(and the request is greater than zero) the ramps which command the heating/cooling are split 
into two successive ramps, the first (half the differential) regulates the free-cooling/free-
heating using the external air shutter, the second regulates the heating/cooling valves. 
 
SUMMER operation/COOLING: Free-Cooling 
 
 
WINTER operation/HEATING: Free-Heating 
 
 
Note. If one of the probes included in the regulation is in error the regulation of the free-
cooling/free-heating can no longer be utilized and the heating/cooling ramp regulate the total 
regulation differential. 
 
 
 
 
 
 
 
Set Point
Delivery
T. Delivery
Pb01
Pb01 / 2
Neutral 
Zone 
100 %
0 %
Cooling coil
External air shutter 
regulated in free-cooling 
Set Point
Delivery
T. Delivery
Pb01
Pb01 / 2
Neutral 
Zone 
100 %
0 %
Heating coil
External air shutter 
regulated in free-heating 
