C-PRO KILO AHU APPLICATION MANUAL
Pag. 79
6.15.7 Last date of maintenance
In the Menu Manutentore->Funzionamento (Maintenance Operator->Operation) you will 
find a page with the ability to memorize the last date of maintenance for the implant. By 
pressing on “Aggiorna” (Update) the old date which is in the system will automatically be 
updated with the new correct date; updating the maintenance date can be done at parameter 
PM90. 
 
6.15.8 Restoring default parameters
Using the procedure “Ripristino parametri”(Restore Parameters) it is possibile to restore all 
the parameters of the implant to their default values. Enter the installation operator Menu-
>Default (accessible only when the machine is shut off) and set the parameter PH15=SI (1) 
“YES (1)” and wait until the value “NO” (0) appears on the display. The system will 
automatically restore all of the parameters. 
After this operation is complete it is necessary to unfeed and refeed the machine in order to 
avoid malfunctions. 
 
6.15.9 Programming key
It is possible to save the values of all the parameters for the implant in the program key with 
the capability of transferring a copy onto one or more compatible instruments. You may 
only save and restore when the machine is turned OFF (OFF_D or OFF_S) connecting the 
key to the programming connector. 
To save a particular parameter map onto the key:
-
Enter the DEFAULT Menu
-
Press the SET (ENTER) key on OK near the voice 
EVKEY Store: the transfer of the parameters onto the key 
is evidenced by the related flashing led light 
-
Wait for the flashing to stop: if the led is green, the 
operation has concluded correctly, otherwise the light will 
be red 
To copy a parameter map from the key onto a compatible 
device: 
-
Enter the DEFAULT Menu
-
Press the SET (ENTER) key on OK near the voice 
EVKEY Restore the transfer of the paramaters from the 
key onto the compatible device, this is evidenced by the 
related flashing led light 
-
Wait for the flashing to stop: if the led is green, the 
operation has concluded correctly, otherwise the light will 
be red 
 
Note. The data saved onto the key includes information on the product and related version 
and methods for transferring parameter maps onto other compatible devices. 
 
 
 