not present
Pb03
Neutral zone for the regulation of temperature
4.0
0.0
20.0
°C
IS-B
Pb05
Maximum shifting for Set Point calculation
running of delivery
0.0
0.0
20.0
°C
IS-B
If Pb05=0
function not
enabled
Pb06
Proportional band for the Set Point calculation
running of delivery
5.0
0.0
20.0
°C
IS-B
Pb10
Opening of heating valves alarm probe delivery
30.0
0.0
100.0
%
IS-B
Pb11
Opening of cooling valves alarm probe delivery
30.0
0.0
100.0
%
IS-B
Pb20
Insertion/release time single stage of resistance
for the post-heating
60
0
999
Sec
IS-B
HUMIDITY
Menu accessible only if PG06>0 or PG12=1
PU02
Neutral zone for the regulation of humidity
6
0
100
%
IS-U
PU03
Differential for the regulation of humidity
10
0
100
%
IS-U
PU04
Integral time for the regulation of
dehumidification (with cold coil)
0
0
999
Sec
IS-U
If PU04=0
ntegral action
not present
PU05
Enable functional limit for the dehumidification
NO (0)
NO (0)
YES (1)
-
IS-U
PU10
Enable humidifier control with delivery
temperature
YES (1)
NO (0)
YES (1)
-
IS-U
PU11
Set Point on the delivery temperature to enable
the humidifier
22.0
PH03
PH04
°C
IS-U
Only if
PU10=1
PU12
Differential on the delivery temperature to
enable the humidifier
3.0
0.0
20.0
°C
IS-U
Only if
PU10=1
VALVES
PV01
Proportional band for regulation of valves
(cooling/heating)
10.0
0.0
30.0
°C
IS-Va
PV02
Integral time for regulation of valves
(cooling/heating)
0
0
999
Sec
IS-Va
If PV02=0
integral action
not present
PV05
Maximum shifting for Set Point calculation
running of delivery
0.0
0.0
10.0
°C
IS-Va
If PV05=0
function not
enabled
PV06
Proportional band for the Set Point calculation
running of delivery
5.0
0.0
20.0
°C
IS-Va
PV10
Opening cooling/heating valves alarm probe
delivery
30.0
0.0
100.0
%
IS-Va
EXTERNAL AIR SHUTTERS
Menu accessible only if PG07>0
PS01
Type of Free-Cooling / Free-Heating
0: Disabled
1: Free-Cooling / Free-Heating in temperature
2: Free-Cooling / Free-Heating heat exchanger
1
0
2
-
IS-SE
PS02
Enable air quality control
NO (0)
NO (0)
YES (1)
-
IS-SE
PS03
Shutter command type
0: Only for Free-Cooling/Free-Heating
1: Only for controlling air quality
2: Priority to the greater of the two requests
3: Average of the two requests
0
0
3
-
IS-SE
PS04
Proportional band for the modulation of the
external air shutters
8.0
0.0
30.0
°C
IS-SE
PS05
Minimum opening for the external air shutters
0.0
0.0
PS06
%
IS-SE
PS06
Maximum opening for the external air shutters
100.0
PS05
100.0
%
IS-SE
PS07
Run time for the external air shutters from 0% to
100%
120
0
3600
Sec
IS-SE
PS08
Maximum time to maintain signal until end run
time on relay for external air shutters. Signal
will shut off once maximum time is reached
5
0
600
Sec
IS-SE