EVCO c-pro kilo AHU User Manual
Page 45
C-PRO KILO AHU APPLICATION MANUAL
Pag. 45
6.2.3 Unit operation during WINTER/SUMMER WITH
HUMIDITY (PG00=3)
The MOdE parameter can be set up by default in INVERNO (WINTER).
Unit at single coil PG01=1.
The fan regulations can be set up by default in inverter with On/Off (PF01=3).
The primary regulation can be set up by default on the valve (PG04=1).
The primary regulation starts with valves set on default (PG04=1).
The regulation of the shutter is enabled for free-cooling/free-heating (PG07=1, PS01=1).
PIN
ANALOGUE INPUTS
AI1
Ambient air temperature probes (NTC)
AI2
Air delivery temperature probes (NTC)
AI3
External air temperature (NTC)
AI4
Humidity probe (4..20 mA)
AI5
Air expulsion temperature probe (NTC)
PIN
DIGITAL INPUTS
DI1
On/Off remote
DI2
Remote communication summer/winter
DI3
Thermal delivery fan
DI4
Air filter pressure switch
DI5
Anti-freeze thermostat
DI6
Air-flow meter
DI7
Thermal pickup fan
PIN
ANALOGUE OUTPUTS
AO 1
Not utilized
AO 2
Cooling/heating valve control (0-10V)
AO 3
Inverter fan control (0-10V)
PIN
DIGITAL OUTPUTS
DO1
Delivery fan
DO2
Pickup fan
DO3
Humidifier on/off
DO4
Opening external air shutters
DO5
Closing external air shutters
DO6
Dirty filter indicator
DO7
Configurable alarms (all active alarms)
RTC system clock present.