beautypg.com

EVCO c-pro kilo AHU User Manual

Page 45

background image

C-PRO KILO AHU APPLICATION MANUAL

Pag. 45

6.2.3 Unit operation during WINTER/SUMMER WITH
HUMIDITY (PG00=3)


The MOdE parameter can be set up by default in INVERNO (WINTER).
Unit at single coil PG01=1.
The fan regulations can be set up by default in inverter with On/Off (PF01=3).
The primary regulation can be set up by default on the valve (PG04=1).
The primary regulation starts with valves set on default (PG04=1).
The regulation of the shutter is enabled for free-cooling/free-heating (PG07=1, PS01=1).

PIN

ANALOGUE INPUTS

AI1

Ambient air temperature probes (NTC)

AI2

Air delivery temperature probes (NTC)

AI3

External air temperature (NTC)

AI4

Humidity probe (4..20 mA)

AI5

Air expulsion temperature probe (NTC)

PIN

DIGITAL INPUTS

DI1

On/Off remote

DI2

Remote communication summer/winter

DI3

Thermal delivery fan

DI4

Air filter pressure switch

DI5

Anti-freeze thermostat

DI6

Air-flow meter

DI7

Thermal pickup fan

PIN

ANALOGUE OUTPUTS

AO 1

Not utilized

AO 2

Cooling/heating valve control (0-10V)

AO 3

Inverter fan control (0-10V)

PIN

DIGITAL OUTPUTS

DO1

Delivery fan

DO2

Pickup fan

DO3

Humidifier on/off

DO4

Opening external air shutters

DO5

Closing external air shutters

DO6

Dirty filter indicator

DO7

Configurable alarms (all active alarms)


RTC system clock present.