REGULATIONS
6.1
Unit status
There are additional procedures for the start-up/shut-down of the unit:
1)
Using the On/Off key (parameter, PH05=1)
Startup: press the related key for approximately 2 seconds: if all the other enabled
conditions are present, the machine will turn “ON”.
Shutdown: press the related key for approximately 2 seconds: the machine will turn
“OFF”.
2)
Using the On/Off command from the Digital inputs (parameter, PH07=1)
Startup: close the remote On/Off contact: if all the other enabled conditions are
present, the machine will turn “ON”.
Shutdown: if the remote On/Off contact opens, the machine will turn “OFF from
Digital inputs” (as also indicated by the dictation “OFF_D”).
3)
Using the supervision protocol (parameter, PH09=1)
Startup: activate from protocol the startup status: if all the other enabled conditions
are present, the machine will turn “ON”.
Shutdown: if the startup status becomes deactivated from the protocol, the machine
will turn “OFF da protocollo di supervisione” (OFF from supervision protocol) (as
also indicated by the dictation “OFF_S”).
The status of the On/Off key has priority with respect to the other two keys. In fact, the
status of the On/Off from Digital Inputs and from supervision protocol are accessible only
when the machine’s keyboard is turned on.
A machine with its Digital inputs shut off can:
⋅
Change to OFF status by pressing the ESC key.
⋅
Change to OFF status as supervisor if you re-enter the conditions of OFF from Digital
inputs and set the status of OFF from supervisor.
⋅
Change to ON status if you re-enter the conditions of OFF from Digital inputs and do
not set the status of OFF from supervisor.
A machine with its supervision protocol shut off can:
⋅
Change to OFF status by pressing the ESC key.
⋅
Change to status OFF from Digital inputs if you re-enter the conditions of OFF from
supervisor and switch the status of OFF from Digital inputs.
⋅
Change to ON status if you re-enter the conditions of OFF from supervisor and the
conditions of OFF from Digital inputs are not present.
The machines On/Off key is the ESC key, which needs to be pressed down for approximately
2 seconds.
The remote On/Off inputs (if present) can be configured through the following parameters:
-
PH07: Enable the function
-
PH50: Set the logic NC, NO for the digital contacts
-
Hd01: Set the position for the Digital inputs