EVCO c-pro kilo AHU User Manual
Page 37

C-PRO KILO AHU APPLICATION MANUAL
Pag. 37
PH52
Logistics of Digital inputs used for the alarm 
flux status 
NC (1)
NO (0)
NC (1)
-
IS-V
PH53
Logistics of Digital inputs for alarm fire-smoke
NC (1)
NO (0)
NC (1)
-
IS-V
PH60
Logistics of alarm relay
NO (0)
NO (0)
NC (1)
-
IS-V
PH15
Restoring the manufacturers’ defualt parameters
NO (0)
NO (0)
YES (1)
-
IS-D
Wait for the 
value NO(0) 
upon 
completion of 
restore 
PSd3
Password Installation Operator Level (3)
0
-999
9999
-
IS
Level
4
CONSTRUCTOR MENU
CONFIGURATION PARAMETERS
Upon modification of these parameters it is
advised to remove and delete the card feed
PG00
Unit type: 
1: Winter operating mode only 
2: Summer operating mode only 
3: Winter and summer operating mode with 
humidity 
4: Winter and summer operating mode with 
humidity and heat recuperation 
5: Two coils without dehumidification 
6: Three coils with dehumidification 
3
1
6
-
CO-W
PG01
Number of coils 
1: Heating/Cooling (Unit with single coil) 
2: Heating, Cooling 
3: Heating, Cooling, Post-Heating 
1
1
3
-
COW
If PG01=1 the 
MOdE 
parameter 
decides if hot 
or cold 
PG02
Enable the presence of the expansion
NO (0)
NO (0)
YES (1)
-
CO-W
PG03
Enable RTC system clock
YES (1)
NO (0)
YES (1)
-
CO-W
If PG03=0, 
history does 
not memorize 
elements and 
the nocturnal 
operating 
mode is 
disabled 
PG04
Primary types of regulation: 
0: On fan 
1: On valves 
Valv. (1)
Fan (0)
Valv. (1)
-
CO-W
PG05
Positioning probe of regulation: 
0: Ambient probe 
1: Probe in restart channel 
Amb. (0)
Amb. (0)
Rest. (1)
-
CO-W
PG06
Enable humidifier 
0: Disabled 
1: Regulation ON-OFF 
2: Regolation Modulating 
1
0
2
-
CO-W
PG07
Enabled external air shutters 
0: Disabled 
1: Modulating regulation 
2: Fixed opening 
1
0
2
-
CO-W
PG08
Enable delivery fans
YES (1)
NO (0)
YES (1)
-
CO-W
PG09
Enable pickup fans
YES (1)
NO (0)
YES (1)
-
CO-W
PG10
Enable heating circulation pump (or single pump 
for the unit at single coil) 
NO (0)
NO (0)
YES (1)
-
CO-W
PG11
Enable cooling circulation pump
NO (0)
NO (0)
YES (1)
-
CO-W
PG12
Enable dehumidification
NO (0)
NO (0)
YES (1)
-
CO-W
PG13
Manage heating recuperator
0
0
4
-
CO-W