C-PRO KILO AHU APPLICATION MANUAL

Pag. 27

4.2.9 Main ON page

When the unit is turned ON the following main pages will appear:








from which you may access the status page, by pressing ENTER on the “>”. By pressing the
ESC key you will able to view the alarm and history pages.

The Set Point viewed is that which is presently in use by the regulations and is calculated by
the relative parameters based on the modes of operation (SEtC, SEtH) and by the possible
variations introduced from the relative functions (compensation, evening time mode, digital
inputs, supervisor).

Additionally, the page includes certain information relating to functions which have yet to
become active:

cR:

Compensation Set Point summer

tR:

Variation Set Point in nocturnal operating mode

dR:

Variation Set Point from digital inputs

sR:

Variation Set Point from supervisor

sF:

Active fans for cycles of air quality control sensors

LD:

The dehumidification functional limit is active
The external air shutters are active for free-cooling
The external air shutters are active for free-heating
The external air shutters are active for air quality control
The external air shutters are active for free-cooling/free-
heating and for air quality control (the maximum
requested)
The external air shutters are active for free-cooling/free-
heating and for air quality control (the average requested)

FC:
FH:
QA:
MX:

MD:

FX:

The external air shutters are active in a fixed opening

The function is active if the related code is visible in the page.

4.2.10 Status page

From the main page it is possible to scroll through the various pages and have open access to
view the status of each device in operation.
These pages are not password protected and are only accessible when the unit is ON. To
view, press ENTER on “>” on the main ON page.
To scroll the status pages press ENTER on the the label “<” to return to a preceding page or
on the label “>” to view a successive page.



Mode of operation during summer/winter

Active functions on the unit

Set Point ambient temperature
Set Point ambient humidity

If ALARM indicates that there are active
alarms