C-PRO KILO AHU APPLICATION MANUAL

Pag. 32

activate

PM80

Calibration of the ambient air temperature probe

0.0

-10.0

10.0

°C

MA-IO

PM81

Calibration of the delivery air temperature probe

0.0

-10.0

10.0

°C

MA-IO

PM82

Calibration of the external air temperature probe

0.0

-10.0

10.0

°C

MA-IO

PM83

Calibration of the ambient humidity probe

0

-10

10

°C

MA-IO

PM84

Calibration of the air temperature expulsion
probe

0.0

-10.0

10.0

°C

MA-IO

PM85

Calibration of the anti-freeze temperature probe

0.0

-10.0

10.0

°C

MA-IO

PM87

Calibration of the pre-heating air temperature
probe

0.0

-10.0

10.0

°C

MA-IO

PM88

Calibration of the air quality probe (CO2/VOC)

0

-100

100

ppm

MA-IO

PM89

Calibration of the external air humity probe

0

-10

10

%

MA-IO

PSd2

Password Maintenance Operator Level (2)

0

-999

9999

-

MA

Level
3

INSTALLATION OPERATOR MENU

REGULATION

PC01

Enable compensation Set Point summer

NO (0)

NO (0)

YES (1)

-

IS-R

PC02

Set Point maximum for summer compensation

28.0

SEtC

PH04

°C

IS-R

PC03

Set Point (on external t.) from begining
compensation

26.0

PH03

PH04

°C

IS-R

PC04

Differential for the summer compensation of Set
Point

4.0

0.0

20.0

°C

IS-R

PC05

Enable cycles for air quality sensors for ambient
temperature (when probe is restarting)

NO (0)

NO (0)

YES (1)

-

IS-R

PC06

Wait time prior to fan activation for air quality
sensors

6

1

99

Min

IS-R

PC07

Fan activation time for air quality sensors

2

1

30

Min

IS-R

PC08

Activate both fans for air quality sensors
0 : NO – Only activate pickup fan
1 : YES – Activate both fans

NO (0)

NO (0)

YES (1)

-

IS-R

Only with
PG05=1

FANS

PF01

Types of regulations for fans:
0: Continuous Regulation
1: On/Off Regulation
2: Module Regulation
3: Module Regulation with steps to enable
On/Off

1

Continuo

us (0)

Inverter+

OnOff

(3)

-

IS-F

PF02

Differentials for fan regulation

5.0

0.0

30.0

°C

IS-F

PF03

Minimum speed for the regulation of fan
modules

0.0

0.0

PF04

%

IS-F

PF04

Maximum speed for the regulation of fan
modules

100.0

PF03

100.0

%

IS-F

PF05

Minimum time between the startup of pickup
and delivery fans.

20

0

999

Sec

IS-F

PF08

Differentials of On/Off steps on ramp of
regulation of fan modules

8.0

PF03

60.0

%

IS-F

Only if
PF01=3

PF09

Wait time (on and off) of On/Off steps on ramp
of regulation of fan modules

10

0

999

Sec

IS-F

Only if
PF01=3

PF10

Pickup and delivery fan speed in ambient probe
alarm

30.0

0.0

100.0

%

IS-F

If fans
On/Off set
PF10 > 0 to
activate in
probe error

COILS

Pb01

Proportional band for regulation of valves
(cooling/heating)

10.0

0.0

20.0

°C

IS-B

Pb02

Integral time for regulation of valves
(cooling/heating)

0

0

999

Sec

IS-B

If Pb02=0
integral action