EVCO c-pro kilo AHU User Manual
Page 32
C-PRO KILO AHU APPLICATION MANUAL
Pag. 32
activate
PM80
Calibration of the ambient air temperature probe
0.0
-10.0
10.0
°C
MA-IO
PM81
Calibration of the delivery air temperature probe
0.0
-10.0
10.0
°C
MA-IO
PM82
Calibration of the external air temperature probe
0.0
-10.0
10.0
°C
MA-IO
PM83
Calibration of the ambient humidity probe
0
-10
10
°C
MA-IO
PM84
Calibration of the air temperature expulsion
probe
0.0
-10.0
10.0
°C
MA-IO
PM85
Calibration of the anti-freeze temperature probe
0.0
-10.0
10.0
°C
MA-IO
PM87
Calibration of the pre-heating air temperature
probe
0.0
-10.0
10.0
°C
MA-IO
PM88
Calibration of the air quality probe (CO2/VOC)
0
-100
100
ppm
MA-IO
PM89
Calibration of the external air humity probe
0
-10
10
%
MA-IO
PSd2
Password Maintenance Operator Level (2)
0
-999
9999
-
MA
Level
3
INSTALLATION OPERATOR MENU
REGULATION
PC01
Enable compensation Set Point summer
NO (0)
NO (0)
YES (1)
-
IS-R
PC02
Set Point maximum for summer compensation
28.0
SEtC
PH04
°C
IS-R
PC03
Set Point (on external t.) from begining
compensation
26.0
PH03
PH04
°C
IS-R
PC04
Differential for the summer compensation of Set
Point
4.0
0.0
20.0
°C
IS-R
PC05
Enable cycles for air quality sensors for ambient
temperature (when probe is restarting)
NO (0)
NO (0)
YES (1)
-
IS-R
PC06
Wait time prior to fan activation for air quality
sensors
6
1
99
Min
IS-R
PC07
Fan activation time for air quality sensors
2
1
30
Min
IS-R
PC08
Activate both fans for air quality sensors
0 : NO – Only activate pickup fan
1 : YES – Activate both fans
NO (0)
NO (0)
YES (1)
-
IS-R
Only with
PG05=1
FANS
PF01
Types of regulations for fans:
0: Continuous Regulation
1: On/Off Regulation
2: Module Regulation
3: Module Regulation with steps to enable
On/Off
1
Continuo
us (0)
Inverter+
OnOff
(3)
-
IS-F
PF02
Differentials for fan regulation
5.0
0.0
30.0
°C
IS-F
PF03
Minimum speed for the regulation of fan
modules
0.0
0.0
PF04
%
IS-F
PF04
Maximum speed for the regulation of fan
modules
100.0
PF03
100.0
%
IS-F
PF05
Minimum time between the startup of pickup
and delivery fans.
20
0
999
Sec
IS-F
PF08
Differentials of On/Off steps on ramp of
regulation of fan modules
8.0
PF03
60.0
%
IS-F
Only if
PF01=3
PF09
Wait time (on and off) of On/Off steps on ramp
of regulation of fan modules
10
0
999
Sec
IS-F
Only if
PF01=3
PF10
Pickup and delivery fan speed in ambient probe
alarm
30.0
0.0
100.0
%
IS-F
If fans
On/Off set
PF10 > 0 to
activate in
probe error
COILS
Pb01
Proportional band for regulation of valves
(cooling/heating)
10.0
0.0
20.0
°C
IS-B
Pb02
Integral time for regulation of valves
(cooling/heating)
0
0
999
Sec
IS-B
If Pb02=0
integral action