C-PRO KILO AHU APPLICATION MANUAL
Pag. 51
6.3
Operating mode during summer/winter
 
The operating modes can assume the following values: 
 
Parameter “MOdE”
Description
0=COOL – SUMMER
Summer operation
1=HEAT – WINTER
Winter operation
 
There are additional procedures which allow you to set the operating mode of the unit: 
1)
Using the MOdE parameter in the user Menu (function enabled by using parameter 
PH06) 
Set – Positioned on the ModE parameter, press the ENTER key, modify the values 
using the UP and DOWN keys. Confirm by pressing the ENTER key again. 
 
2)
Using the command Summer/Winter from Digital inputs (function enabled by 
using parameter PH08 and parameter Hd02 to stabilize the position of associated 
Digital inputs) 
Set - With open contact the unit is in “winter” operating mode, with closed contact 
the unit is in “summer” operating mode. 
 
3)
Using the supervision protocol (enabled by using parameter PH10)
Set - Enter from protocol, through relative status, the change command for the 
operating mode. 
 
Note. It is advisable to carry out the change the summer/winter operating modes while the 
machine is shut down. 
 
 
 