EVCO c-pro kilo AHU User Manual
Page 35

C-PRO KILO AHU APPLICATION MANUAL
Pag. 35
PA01
Enable alarms during hours of fan operation
YES (1)
NO (0)
YES (1)
-
IS-S
PA02
Enable alarms during hours of pump operation
NO (0)
NO (0)
YES (1)
-
IS-S
PA03
Signal alarms during hours of operation on 
alarm relay 
YES (1)
NO (0)
YES (1)
-
IS-S
PA04
Probe alarm delay
10
0
240
Sec
IS-S
PA05
Signal alarm probe on alarm relay
YES (1)
NO (0)
YES (1)
-
IS-S
PA06
Expansion alarm delay
5
0
999
Sec
IS-S
PA08
Signal delivery fan alarm on alarm relay
YES (1)
NO (0)
YES (1)
-
IS-S
PA09
Signal pickup fan alarm on alarm relay
YES (1)
NO (0)
YES (1)
-
IS-S
PA10
Alarm delay thermal fans
2
0
999
Sec
IS-S
PA11
Alarm delay inverter fans
2
0
999
Sec
IS-S
PA15
Alarm delay thermal pumps
2
0
999
Sec
IS-S
PA16
Signal alarms thermal pumps on alarm relay
YES (1)
NO (0)
YES (1)
-
IS-S
PA20
Type of pressure switch alarm re-arm (dirty 
recuperator) 
0: Auto - Automatic 
1: Manu - Manual 
Manu (1)
Auto (0)
Manu (1)
-
IS-S
PA21
Pressure switch alarm delay (dirty recuperator)
30
0
999
Sec
IS-S
PA24
Type of alarm re-arm pressure switch air filter 
0: Auto - Automatic 
1: Manu - Manual 
Manu (1)
Auto (0)
Manu (1)
-
IS-S
PA25
Pressure switch air filter alarm delay
30
0
999
Sec
IS-S
PA26
Signal alarms pressure switch air filter alarm 
relay 
YES (1)
NO (0)
YES (1)
-
IS-S
PA28
Reset airflow meter alarm delay
30
0
999
Sec
IS-S
PA29
Airflow meter alarm delay
5
0
999
Sec
IS-S
PA30
Signal alarm air flow meter on alarm relay
YES (1)
NO (0)
YES (1)
-
IS-S
PA31
Type of humidifier alarm re-arm 
0: Auto - Automatic 
1: Manu - Manual 
Auto (0)
Auto (0)
Manu (1)
-
IS-S
PA32
Humidifier alarm delay
2
0
999
Sec
IS-S
PA33
Signal alarms humidifier on alarm relay
YES (1)
NO (0)
YES (1)
-
IS-S
PA35
Type of anti-freeze alarm management: 
0: Disabled 
1: From digital contact 
2: From anti-freeze probe 
1
0
2
-
IS-S
PA36
Alarm delay anti-freeze
5
0
999
Sec
IS-S
PA37
Signal alarm anti-freeze on alarm delay
YES (1)
NO (0)
YES (1)
-
IS-S
PA38
Activation Set Point for anti-freeze alarm from 
transducer 
2.0
PH03
PH04
°C
IS-S
PA39
Activation differential for anti-freeze alarm from 
transducer 
3.0
0.0
10.0
°C
IS-S
PA40
Enable RTC alarm
YES (1)
NO (0)
YES (1)
IS-S
PA41
Type of RTC alarm restoration 
0: Auto - Automatic 
1: Manu - Manual 
Manu (1)
Auto (0)
Manu (1)
-
IS-S
PA42
Signal RTC alarms on alarm relay
YES (1)
NO (0)
YES (1)
-
IS-S
PA45
Signal alarms fire/smoke on alarm relay
YES (1)
NO (0)
YES (1)
-
IS-S
VARIOUS PARAMETERS
PH01
Minimum value threshold for the pressure 
probe 
0
-10.0
PH02
Bar
IS-V
PH02
Maximum value threshold for the pressure 
probe 
30.0
PH01
45.0
Bar
IS-V
PH03
Minimum temperature value for the Set Point
-5.0
-15.0
PH04
°C
IS-V
PH04
Maximum temperature value for the Set Point
40.0
PH03
70.0
°C
IS-V
PH05
Enable machine start-up/shut-down by pressing 
the ESC/Stand-By key 
YES (1)
NO (0)
YES (1)
-
IS-V
PH06
Enable the change in summer/winter operating
YES (1)
NO (0)
YES (1)
-
IS-V