C-PRO KILO AHU APPLICATION MANUAL

Pag. 43

6.2.1 Unit in WINTER operating mode (PG00=1)


The MOdE parameter can be setup by default in INVERNO (WINTER).
Unit at single coil PG01=1.
The fan regulations can be setup by default in On/Off (PF01=1).
The primary regulation can be setup by default on the valve (PG04=1).
The regulation of the shutter is fixed (PG07=2).

PIN

ANALOGUE INPUTS

AI1

Ambient air temperature probes (NTC)

AI2

Air delivery temperature probes (NTC)

AI3

Not utilized

AI4

Not utilized

AI5

Not utilized

PIN

DIGITAL INPUTS

DI1

On/Off remote

DI2

Not utilized

DI3

Thermal delivery fan

DI4

Air filter pressure switch

DI5

Anti-freeze thermostat

DI6

Airflow status

DI7

Not utilized

PIN

ANALOGUE OUTPUTS

AO 1

Not utilized

AO 2

Heating valve control (0-10V)

AO 3

Not utilized

PIN

DIGITAL OUTPUTS

DO1

Delivery fan

DO2

Pickup fan

DO3

Not utilized

DO4

Opening external air shutters

DO5

Closing external air shutters

DO6

Dirty filter indicator

DO7

Alarm


RTC system clock