beautypg.com

EVCO c-pro kilo AHU User Manual

Page 39

background image

C-PRO KILO AHU APPLICATION MANUAL

Pag. 39

HE02

Position of the digital output of the second stage
of electrical resistance

0

0

14

-

CO-HO

HE03

Position of the digital output of the third stage of
electrical resistance

0

0

14

-

CO-HO

HA01

Position of the digital output of the alarm relay

7

0

14

-

CO-HO

HA02

Position of the digital output for dirty filter
indicator alarm or dirty recuperator

6

0

14

-

CO-HO

HA04

Position of the analogue output of the heating
valves (or single for heating/cooling in case the
unit is at single coil)

2

0

6

-

CO-HO

HA05

Position of the analogue output of the
cooling/dehumidifying valve

0

0

6

-

CO-HO

HA06

Position of the analogue output of the post-
heating valves

0

0

6

-

CO-HO

HA07

Positioning of Analogue outputs for the inverter
fans

3

0

6

-

CO-HO

HA08

Positioning of Analogue outputs for the
humidifier module

0

0

6

-

CO-HO

HA09

Position of the analogue output dedicated for the
rotating recuperator

0

0

6

-

CO-HO


Note.
In order to accurately configure the machine parameters, it is advised that the card feed
be removed/deleted once the machine parameters have been configured and for each
subsequent modification to the “ parametri di configurazione” (configuration parameters).