EVCO c-pro kilo AHU User Manual
Page 16
C-PRO KILO AHU APPLICATION MANUAL
Pag. 16
JD:
Connection for the cut-phase output EVDFAN1 (analogue output 1; not utilized)
Conn.
Label
Description
JD-1
VDC
Supplying power to cut-phase module EVDFAN1
JD-2
AO1
Cut-phase output module EVDFAN1
In order to utilize the cut-phase module EVDFAN1, it is necessary to supply power to the
controller in an alternate current; the current that powers the controller must be the same
current as that which is used to power the module.
JE:
Connections for analogue outputs 2 and 3 (opto-isolator)
Conn.
Label
Description (Version V+V)
JE-1
AO2
0-10VDC
JE-2
GND
Common analogue outputs
JE-3
AO3
0-10VDC
JF:
Connections for controller power supply
Conn.
Label
Description
JF-1
V
≅
Controller power supply (24VAC / 20 … 60 VDC)
JF-2
V
≅
Controller power supply (24VAC / 20 … 60 VDC)
JG:
Connections for network expansion I/O (not utilized) and for the remote keyboard (not
utilized)
Conn.
Label
Description
JG-1
VDC
Remote keyboard power supply (12VDC, max. 50 mA)
JG-2
GND
Common
JG-3
DATA
Serial in tension
JM-JL-JI-JH
: Connection for digital outputs
Conn.
Label
Description
JM-4
NO1
Contact normally open - output n.1
JM-3
CO1
Common output n.1
JM-2
NO2
Contact normally open - output n.2
JM-1
CO2
Common output n.2
JL-4
NO3
Contact normally open - output n.3
JL-3
CO3
Common output n.3
JL-2
NO4
Contact normally open - output n.4
JL-1
CO4
Common output n.4
JI-4
NO5
Contact normally open - output n.5
JI-3
CO5
Common output n.5
JI-2
NO6
Contact normally open - output n.6
JI-1
CO6
Common output n.6
JH-3
NO7
Contact normally open - output n.7
JH-2
NC7
Contact normally closed - output n.7
JH-1
CO7
Common output n.7