beautypg.com

8modbus variables, 1 modbus export table – EVCO c-pro kilo AHU User Manual

Page 84

background image

C-PRO KILO AHU APPLICATION MANUAL

Pag. 84

8

MODBUS VARIABLES


It is possible to control the application using a supervisor, utilizing the Modbus protocol. The
communication comes across an interface (serial RS485) which is already integrated in the
controller. To follow are the various states/parameters exported by the application.

8.1

ModBus Export Table

Addr

Name

Value

Min

Max

Description

Mode

257

Packed_DI

0

0

65535

Bit1=DI1,
Bit2=DI2,
Bit3=DI3,
Bit4=DI4,
Bit5=DI5,
Bit6=DI6,
Bit7=DI7

R/W

385

Packed_DO

0

0

65535

Bit1=DO1,
Bit2=DO2,
Bit3=DO3,
Bit4=DO4,
Bit5=DO5,
Bit6=DO6,
Bit7=DO7

R/W

513

AI01_Evironment_Probe

0.0

-3276.8

3276.7

R/O

514

AI02_AirSupply_Probe

0.0

-3276.8

3276.7

R/O

515

AI03_AirExternal_Probe

0.0

-3276.8

3276.7

R/O

516

AI04_HumidityEnvironment_Probe

0

-32768

32767

R/O

517

AI05_AirPressureSupply_Probe

0.0

-3276.8

3276.7

R/O

641

AO_InverterFan

0.00

0.00

100.00

R/W

642

AO_ValveRequest

0.00

0.00

100.00

R/W

643

AO_Humidifier

0.00

0.00

100.00

R/W

769

PackedAlarm_1

0

0

65535

Bit1=AL01,
Bit2=AL02,
Bit3=AL03,
Bit4=AL04,
Bit5=AL05,
Bit6=AL06,
Bit7=AL07,
Bit8=AL08,
Bit9=AL09,
Bit10=AL10,
Bit11=AL11,
Bit12=AL12,
Bit13=AL13,
Bit14=AL14,
Bit15=AL15,
Bit16=AL16

R/W