C-PRO KILO AHU APPLICATION MANUAL

Pag. 81

7.2

Table of Alarms


The following is a list of all the alarms managed by the application. The order of
presentation is the same as the order of presentation for the active alarms. All alarms can be
viewed even when the mahcine is off.

Code

Description of alarm

Re-arm

Consequence

Delay

AL01

Thermal delivery fan (*²)

Auto

Shuts down all devices

Fixed 2 sec.

AL02

Thermal pickup fan (*²)

Auto

Shuts down all devices

Fixed 2 sec.

AL03

Alarm inverter delivery fan (*²)

Auto

Shuts down all devices

Fixed 2 sec.

AL04

Alarm inverter pickup fan (*²)

Auto

Shuts down all devices

Fixed 2 sec.

AL05

Thermal circulation pump

Auto

Stops the pump

Fixed 2 sec.

AL08

Air filter pressure switch

A/M

Visualization

May be set

AL09

Humidifier

A/M

Stops the humidifier

May be set

AL10

Airflow meter (*²)

Manu

Shuts down all devices

May be set

AL11

Anti-freeze

Auto

Shuts down fans and closes the
shutter
Forces heating coil to 100%
Forces cooling coil to 0%

May be set

AL13

Fire/smoke Alarm (*²)

Auto

Shuts down all devices

-

AL14

Operating hours – delivery fans

Manu*¹

Visualization

-

AL15

Hours of operation – Uptake fan

Manu*¹

Visualization

-

AL16

Hours of operation – Heating pump

Manu*¹

Visualization

-

AL17

Hours of operation – Cooling pump

Manu*¹

Visualization

-

AL18

Ambient air probe broken or disconnected

Auto

Inhibits the regulations upon
which the probe is dependent

May be set

AL19

Air delivery probe broken or disconnected

Auto

Inhibits the regulations upon
which the probe is dependent

May be set

AL20

External air probe broken or disconnected

Auto

Inhibits the regulations upon
which the probe is dependent

May be set

AL21

Ambient humidity probe broken or
disconnected

Auto

Inhibits the regulations upon
which the probe is dependent

May be set

AL22

Air delivery pressure probe broken or
disconnected

Auto

Inhibits the regulations upon
which the probe is dependent

May be set

AL23

Anti-freeze temperature probe damaged or
disconnected

Auto

Inhibits the regulations upon
which the probe is dependent

May be set

AL25

Pre-heating air temperature probe damaged
or disconnected

Auto

Inhibits the regulations upon
which the probe is dependent

May be set

AL26

VOC probe (or CO2) damaged or
disconnected

Auto

Inhibits the regulations upon
which the probe is dependent

May be set

AL27

External air humidity probe damaged or
disconnected

Auto

Inhibits the regulations upon
which the probe is dependent

May be set

AL28

RTC Alarm broken or discharged

A/M

Inibits management of the time
zone

-

AL29

Expansion alarm

Auto

Stops devices on expansion

May be set

A/M: Automatic or Manual alarm (set from parameter)
(*¹) To re-arm alarms connected to the hours of operation you need only reset the hours on the device

to zero.

(*²) These alarms cause the unit to shutdown bringing it to the status OFF from alarm


Note.
To activiate the alarms derived from the digital contacts you need to set to a value
greater than zero the relative position for which the dedicated digital inputs will be
connected. If the position is zero the alarm is not managed. A position may be repeated only
once; it is not possible to manage the same position like “OR” for additional alarms.