Toshiba – Toshiba LF494 User Manual
Page 82
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

TOSHIBA
6 F 8 A 0 7 7 4
■ To change the empty pipe alarm enable/disable status
(Converter for Special specifications):
The following excunple shows how (o change empty alarm from NOJ to N0,0.
Key operation
Display example
Description
SET
□
Jt: EMPTY ALM
1:0N LEVEL!
Press [SET] first to start the items selection sequence
and select Jl: EMPTY ALM from among the
configuration items using
\
► ] and
[-^]
keys. Then
press [SET] again to display the current empiy pipe
alarm enable/clisable status. (In this example ON
LEVELl will be displayed,)
►
□
Jl: EMPTY ALH
1:0N LEVEL!
Pressing [ ► j. the cursor appears.
▲
□
Jl: EMPTY ALM
0:OFF
Select ‘'0:OFF” by pressing [
a
].
SRT
Jl: EMPTY ALH
0:OFF
Pressing [SET], the cursor disappears and the selected
status display flickers. Press [SET] again to save the
Status.
SKJ’
□
Jl: EMPTY ALH
Pressing [SET], the system returns to the items
selection sequence.
-
81
-