S.4 Wiring Procedure
Cable termination and cable connections are described below.
5A1 Cable Terminationi
A CAUTION
■ Ho not con d net w i ri n g work wt e n
■ Eto not w'ork on piping and wiring
power is applied.
with wet hands.
Wiring while power is ap-
Wet hands may result in
1
plied can cause clccinc
1
electric shock.
shock.
DONT
DONT
IMPORTANT
Ttic apparatus should not be provided with the cable glands.
Please prepare yourself for the cable glands which could be used in Division2 hazardous
locations.
Use cables as specified in Table
5 . 1 ^
First, Remove the cable sheath about 70 mm from the
end to expose the coated wires and then strip the wires about 10 [nm. Then attach an
M4-sis:e compression terminal lug to the end of each wire using a compression tool. The
compression terminal should be of Ihe kind with insulated sleeve to prevent shorts between
adjacent terminals. The overall length oi thc wire with the terminal attached should be about
6
(.) nmi. Sec Figure .‘5,4 below,
M4-sizc compression terminal lug