beautypg.com

Bus regulation – Rockwell Automation 20B PowerFlex 70, PowerFlex 700 Reference Manual User Manual

Page 56

background image

Bus Regulation

56

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

Bus Regulation

[Bus Reg Gain]
[Bus Reg Mode A, B]

Some applications, such as the hide tanning shown here, create an intermittent
regeneration condition. When the hides are being lifted (on the left), motoring
current exists. However, when the hides reach the top and fall onto a paddle, the
motor regenerates power back to the drive, creating the potential for a nuisance
overvoltage trip.

When an AC motor regenerates energy from the load, the drive DC bus voltage
increases unless there is another means (dynamic braking chopper/resistor, etc.)
of dissipating the energy.

Without bus regulation, if the bus voltage exceeds the operating limit established
by the power components of the drive, the drive will fault, shutting off the output
devices to protect itself from excess voltage.

With bus regulation enabled, the drive can respond to the increasing voltage by
advancing the output frequency until the regeneration is counteracted. This
keeps the bus voltage at a regulated level below the trip point.

Since the same integrator is used for bus regulation as for normal frequency ramp
operation, a smooth transition between normal frequency ramp operation and
bus regulation is accomplished.

The regulator senses a rapid rise in the bus voltage and activates prior to actually
reaching the internal bus voltage regulation set point Vreg. This is important
since it minimizes overshoot in the bus voltage when bus regulation begins
thereby attempting to avoid an over-voltage fault.

Motoring

Regenerating

0V Fault @V

bus

Max

Drive Output Shut Off

Ch1

Ch3

Single Seq 500 S/s

100mV

500mV

Ch2

100mV

M 1.00s

Ch3

1.47 V

3

2

1

This manual is related to the following products: