Torque Performance Modes
Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013
201
Torque Performance
Modes
[Torque Perf Mode] or [Motor Cntl Sel] (Vector) selects the output mode of the
drive. The choices are:
•
Custom Volts/Hertz
Used in multi-motor or synchronous motor applications.
•
Fan/Pump Volts/Hertz
Used for centrifugal fan/pump (variable torque) installations for additional
energy savings.
•
Sensorless Vector
Used for most general constant torque applications. Provides excellent
starting, acceleration and running torque.
•
Sensorless Vector w/Economizer
Used in constant torque applications that have significant “idle” time (time
spent at greatly reduced load) to offer additional energy conservation.
The following table shows the performance differences between V/Hz and
Sensorless Vector.
Volts/Hertz
Volts/Hertz operation creates a fixed relationship between output voltage and
output frequency. The relationship can be defined in two ways.
1.
Fan/Pump
When this option is chosen, the relationship is 1/X
2
. Therefore;
for full frequency, full voltage is supplied and for ½1/2 rated frequency,
1/4 voltage is applied, etc. This pattern closely matches the torque
requirement of a variable torque load (centrifugal fan or pump – load
increases as speed increases) and offers the best energy savings for these
applications.
2.
Custom
Custom Volts/Hertz allows a wide variety of patterns using linear segments.
The default configuration is a straight line from zero to rated voltage and
frequency. This is the same volts/hertz ratio that the motor would see if it
Torque Mode
Fan/Pump and
Custom V/Hz with
Slip Comp
SVC with Slip
Comp
SVC with
Feedback
Flux Vector
without
Feedback
Flux Vector with
Feedback
Speed Regulation
(% of base speed)
0.5%
0.5%
0.1%
0.1%
0.001%
Operating Speed Range
40:1
80:1
80:1
120:1
1000:1
Speed Bandwidth
10 rad/sec
20 rad/sec
20 rad/sec
50 rad/sec
250 rad/sec
Maximum Voltage
Maximum
Frequency
Base Voltage
(Nameplate)
Base Frequency
(Nameplate)
Run Boost