Exclusive control – Rockwell Automation 20B PowerFlex 70, PowerFlex 700 Reference Manual User Manual
Page 137
Process PI Loop
Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013
137
When the PI is enabled, the output of the PI Controller is added to the ramped
speed reference.
Exclusive Control
Process Control takes the output of PI regulator as the speed command. No
master speed reference exists and the PI Output directly controls the drive
output.
In the pumping application example below, the reference or setpoint is the
required pressure in the system. The input from the transducer is the PI feedback
and changes as the pressure changes. The drive output frequency is then increased
or decreased as needed to maintain system pressure regardless of flow changes.
With the drive turning the pump at the required speed, the pressure is
maintained in the system.
However, when additional valves in the system are opened and the pressure in the
system drops, the PI error will alter its output frequency to bring the process back
into control.
When the PI is disabled the commanded speed is the ramped speed reference.
+
Spd Cmd
Process PI
Controller
Linear Ramp
& S-Curve
+
+
+
PI Enabled
Speed Control
Spd Ref
PI Ref
PI Fbk
Slip Adder
Open
Loop
Slip
Comp
Process
PI
PI Feedback
Motor
Pump
Desired Pressure
[PI Reference Sel]
Pressure
Transducer