Analog Outputs

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

31

Here, the deadband is “shifted” due to the 50 Hz limitation. The command
frequency from 0 to 3 volts on the analog input will be 15 Hz. After 3 volts, the
frequency will increase at a rate of 0.2 volts per hertz up to 9 volts. After 9 volts
on the analog input the frequency command will remain at 45 Hz.

Analog Outputs

Explanation

Each drive has one or more analog outputs that can be used to annunciate a wide
variety of drive operating conditions and values.

The user selects the analog output source by setting [Analog Out Sel].

Configuration

The PowerFlex 70 standard I/O analog output is permanently configured as a
0-10 volt output. The output has 10 bits of resolution yielding 1024 steps. The
analog output circuit has a maximum 1.3% gain error and a maximum 7 mV
offset error. For a step from minimum to maximum value, the output will be
within 0.2% of its final value after 12ms.

The PowerFlex 700 standard I/O analog output is permanently configured as a
0-10 volt output. The output has 10 bits of resolution yielding 1024 steps. The
analog output circuit has a maximum 1.3% gain error and a maximum 100 mV
offset error. For a step from minimum to maximum value, the output will be
within 0.2% of its final value after 12ms.

INPUT

S &

OUTPU

T

S

An

al

og O

utput

s

342
345

[Analog Out1 Sel]

[Analog Out2 Sel]

Selects the source of the value that drives the analog
output.

Default:

Options:

0 “Output Freq”

See Table

001
002
003
004
005
007
006
012
135
136
137
138
220
219

377
378

Vector

* Vector Control Option Only

**Vector firmware 3.001 & later

(1)

Refer to Option Definitions in User Manual.

Options

[Analog Out1 Lo] Value

[Analog Out1 Hi] Value

Param. 341 = Signed

Param. 341 = Absolute

0
1
1*
2
3
4
5
6
7
8
9
10
11
12
13
14*
15*
16*
17*
18*
19*
20-23**
24**

“Output Freq”
“Command Freq”
“Command Spd”
“Output Amps”
“Torque Amps”
“Flux Amps”
“Output Power”
“Output Volts”
“DC Bus Volts”
“PI Reference”

(1)

“PI Feedback”
“PI Error”
“PI Output”
“%Motor OL”
“%Drive OL”
“CommandedTrq”
“MtrTrqCurRef”

(1)

“Speed Ref”
“Speed Fdbk”
“Pulse In Ref”

(1)

“Torque Est”

(1)

“Scale Block1-4”

(1)

“Param Cntl”

(1)

–[Maximum Speed]
–[Maximum Speed]
–[Maximum Speed]
0 Amps
–200% Rated
0 Amps
0 kW
0 Volts
0 Volts
–100%
–100%
–100%
–100%
0%
0%
–800% Rated
–200% Rated
–[Maximum Speed]
–[Maximum Speed]
–25200.0 RPM
–800%

0 Hz
0 Hz
0 Hz/RPM
0 Amps
0 Amps
0 Amps
0 kW
0 Volts
0 Volts
0%
0%
0%
0%
0%
0%
0%
0%
0 Hz/RPM
0 Hz/RPM
0 Hz/RPM
0%

+[Maximum Speed]
+[Maximum Speed]
+[Maximum Speed]
200% Rated
200% Rated
200% Rated
200% Rated
120% Rated Input Volts
200% Rated Input Volts
100%
100%
100%
100%
100%
100%
800% Rated
200% Rated
+[Maximum Speed]
+[Maximum Speed]
+[Maximum Speed]
+800%