Start-Up
188
Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013
Figure 50 PowerFlex 700 Vector Control Option Startup (2)
Start-Up
2. Motr Dat/Ramp
Enter value for
Motor NP Power
123.4 kW
xxx.x <> yyy.y
Start-Up
2. Motr Dat/Ramp
Enter value for
Motor NP Volts
123.4 Volt
xxx.x <> yyy.y
Start-Up
2. Motr Dat/Ramp
Enter value for
Motor NP FLA
+456.78 Amps
xxx.xx <> yyy.yy
Start-Up
2. Motr Dat/Ramp
Enter value for
Motor NP RPM
+456 RPM
xxx <> yyy
Start-Up
2. Motr Dat/Ramp
Enter value for
Motor NP Hertz
60.0 Hz
x.x <> y.y
Start-Up
2. Motr Dat/Ramp
Enter choice for
Power Units
Killowatt
Go to 0-1 (3. Motor
Tests)
Start-Up
2. Motr Dat/Ramp
Enter value for
Accel Time 1
6.0 Secs
0.0 < 60.0 secs
Start-Up
2. Motr Dat/Ramp
Enter value for
Decel Time 1
6.0 Secs
0.0 < 60.0 secs
Start-Up
2. Motr Dat/Ramp
Enter value for
S Curve %
0 %
0 < 100 %
Start-Up
2. Motr Dat/Ramp
Use motor name-
plate data and
required ramp
times for the
following steps.
Flux Vector Start Up (Motor Dat/Ramp)
2-0
Enter
2-1
2-2
Enter
Enter
2-3
Enter
2-4
Enter
2-5
2-6
Enter
2-11
Enter
2-12
2-13
Enter
Enter
Start-Up
2. Motr Dat/Ramp
Enter Stop Mode:
1.Coast
<2.Ramp>
3.Ramp to Hold
4.DC Brake
2-7
Enter
Use formula:
Poles= 120 * NP Hz
NP RPM
as Motor Poles
parameter value.
Stop Mode A =
"DC Brake" or
"Ramp to Hold"?
Start-Up
2. Motr Dat/Ramp
Enter value for
DC Brake Level
1.0 Amps
0.0 < 30.0 Amps
2-8
Yes
Start-Up
2. Motr Dat/Ramp
Enter value for
DC BrakeTime
1.0 Secs
0.0 < 90.0 Secs
2-9
Enter
No
Start-Up
2. Motr Dat/Ramp
Enter choice for
DB Resistor type
Internal
External
2-10
Enter
Enter
Backup
Note
: Depending on selection, set parameter
#161 (Bus Reg Mode A):
None - Bus Reg Mode A = Adj Freq.
Intenal - Bus Reg Mode A = Both, DB 1st.
External - Bus Reg Mode A = Both, DB 1st.
Stop Mode A =
"DC Brake"?
Yes
No
Start-Up
2. Motr Dat/Ramp
Enter value for
Motor Poles
12
xx <> yy
2-14
Note:
- For V/Hz mode, only states 2-0 thru 2-6 & 2-14 are displayed.
- For V/Hz mode, configure Stop Mode A as Coast to Stop.
- Going from state 2-7 to 2-10 directly sets the DC Brake Level/Time
parameters to their default value.
Note
: If Stop Mode A = COAST, then
skip 2-10.
Note
: If Stop Mode A = COAST, then
skip 2-12. If in Quick/Basic mode, then
exit Motor Data/Ramp.
B
= Basic mode
B
B
B
B
B
B
B
Note
: Default should be
NONE
.
B
B