Power Loss
Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013
129
Table 15 PF700 Bus Levels
Note 1:Vtrigger is adjustable, these are the standard values.
Class
200/240V AC
400/480V AC
600/690V AC
Vslew
1.2V DC
2.4V DC
3.0V DC
Vrecover
Vmem – 30V
Vmem – 60V
Vmem – 75V
Vclose
Vmem – 60V
Vmem – 120V
Vmem – 150V
Vtrigger1,2
Vmem – 60V
Vmem – 120V
Vmem – 150V
Vtrigger1,3
Vmem – 90V
Vmem – 180V
Vmem – 225V
Vopen
Vmem – 90V
Vmem – 180V
Vmem – 225V
Vopen4
153V DC
305V DC
382V DC
Vmin
153V DC
305V DC
382V DC
Voff 5
–
200V DC
–
350
400
450
400
450
500
550
600
650
700
AC Input Volts
DC Bus Volts
Recover
Close
Trigger
Open
350
400
450
400
450
500
550
600
650
700
AC Input Volts
DC Bus Volts
Recover
Close
Trigger
Open
Line Loss Mode = Decel
Line Loss Mode = Coast
350
400
450
300
350
400
450
500
550
600
650
700
AC Input Volts
DC Bus Volts
Recover
Close
Trigger
Open
350
400
450
300
350
400
450
500
550
600
650
700
AC Input Volts
DC Bus Volts
Recover
Close
Trigger
Open
Line Loss Mode = Coast
Line Loss Mode = Decel
350
400
450
300
350
400
450
500
550
600
650
700
AC Input Volts
DC Bus Volts
Recover
Close
Trigger
Open
Line Loss Mode = Continue