Scale Blocks

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

155

Parameter Settings

Parameter Links

Example Configuration #2

Setup a scale block to send parameter 415, [Encoder Speed] to Analog Output 1
as a 0-10V signal.

Parameter Settings

Parameter

Value

Description

[Trim In Select]

11, Preset 1

Preset 1 becomes the trim speed

[Scale1 In Hi]

10.0 V

Hi value of Analog In 2

[Scale1 In Lo]

0 V

Lo value of Analog In 2

[Scale1 Out Lo]

0 RPM

Lo value of desired Trim

[Scale2 In Hi]

1800 RPM

Hi value of Commanded Speed (Max Speed)

[Scale2 In Lo]

0 RPM

Lo value of Commanded Speed

[Scale2 Out Hi]

180 RPM

10% of Max Speed

[Scale2 Out Lo]

0 RPM

Corresponds to lo value of Commanded Speed

Destination Parameter

Source Parameter

Description

[Scale1 In Value]

[Analog In2 Value]

We are scaling Analog In 2 for our trim

[Scale2 In Value]

[Commanded Speed]

Use Commanded Speed as Input to Scale Block 2

[Scale1 Out Hi]

[Scale2 Out Value]

Use the output of Scale Block 2 to set the upper limit of Scale
Block 1 output

[Preset Speed 1]

[Scale 1 Out Value]

Use the scaled analog input as the trim reference into Preset
Speed 1

483

482

484

2

485

486

479

101

480

477

476

478

2

481

487

Commanded Speed

Scale2 In Hi

Scale2 Out Hi

Scale2 In Value

Scale2 Out Lo

Scale2 Out

Value

Preset Speed 1

= Link

Analog In2 Value

Scale2 In Lo

Scale1 In Hi

Scale1 Out Hi

Scale1 In Value

Scale1 Out Lo

Scale1 Out

Value

Scale1 In Lo

0

0

300

600

900

1200

1500

1800

1

2

3

4

5

6

7

8

9

10

Analog Out1 Value (Volts)

Scale1 In Value =

Encoder Speed (RPM)

Parameter

Value

Description

[Analog Out1 Sel]

Scale Block1 Out

Scale Block1 Output goes to Analog Out1

[Analog Out1 Hi]

10 V

Hi value of Analog Output 1 corresponding to Hi value of encoder speed

[Analog Out1 Lo]

0 V

Lo value of Analog Output 1 corresponding to Lo value of encoder speed

[Scale1 In Hi]

1800 RPM

Hi value of the encoder speed

[Scale1 In Lo]

0 RPM

Lo value of the encoder speed