Gse signal processing parameters, Gse spectrum parameters – Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual
Page 80
Publication GMSI10-UM013D-EN-P - May 2010
70 Configuration Parameters
gSE Signal Processing Parameters
gSE Spectrum Parameters
gSE Signal Processing Parameters
Parameter Name
Description
Values/Comments
gSE Full Scale
The maximum signal level expected to be processed
by the channel for gSE measurements. This value is
used to determine the programmable gain settings
across each stage of the channel’s analog signal
processing circuit.
10 Volt
Important: Most gSE applications are
well matched to the default gSE Full
Scale setting of 10 volts. However, if
gSE levels in excess of 5 gSE are
observed or anticipated, then we
recommended you increase the Full
Scale setting to 50 Volts to better
match the dynamic range for the
application.
Output Data Unit (XM Serial
Configuration Utility only)
The data units of the measured value.
This value is always set to gSE.
High Pass Filter
Sets the high pass filter to apply to the gSE
measurement. The high pass filter is useful in
removing low frequency signal components that
would dominate the signal. The high pass filter
attenuates all frequencies below a defined
frequency. It allows, or passes, frequencies above
the defined frequency.
Options: 200 Hz
500 Hz
1000 Hz
2000 Hz
5000 Hz
gSE Spectrum Parameters
Parameter Name
Description
Values/Comments
FMAX
Sets the maximum frequency for the gSE spectrum
measurement.
10 to 5000 Hz
Number of Lines
The number of lines or bins in the gSE spectrum
measurement. This determines the frequency
resolution of the gSE spectrum measurement.
Options: 100
200
400
800