beautypg.com

Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual

Page 122

background image

Publication GMSI10-UM013D-EN-P - May 2010

112 DeviceNet Information

XM-122 Assembly Instance 105 Data Format

Byte

Definition

0–3

Channel 1 gSE Overall measurement value

4–7

Channel 2 gSE Overall measurement value

8–11

Channel 1 Overall measurement value

12–15

Channel 2 Overall measurement value

16–19

Current Speed measurement value

20–23

Acceleration measurement value

24–27

Channel 1 1X Vector Magnitude measurement value

28–31

Channel 2 1X Vector Magnitude measurement value

32–35

Channel 1 2X Vector Magnitude measurement value

36–39

Channel 2 2X Vector Magnitude measurement value

40–43

Channel 1 Band 1 measurement value

44–47

Channel 2 Band 1 measurement value

48–51

Channel 1 Band 2 measurement value

52–55

Channel 2 Band 2 measurement value

56–59

Channel 1 Band 3 measurement value

60–63

Channel 2 Band 3 measurement value

64–67

Channel 1 Band 4 measurement value

68–71

Channel 2 Band 4 measurement value

72–75

Channel 1 3X Vector Magnitude measurement value

76–79

Channel 2 3X Vector Magnitude measurement value

80–83

Channel 1 1X Vector Phase measurement value

84–87

Channel 2 1X Vector Phase measurement value

88–91

Channel 1 Not 1X measurement value

92–95

Channel 2 Not 1X measurement value

96–99

Channel 1 Sum Harmonics measurement value

100–103

Channel 2 Sum Harmonics measurement value

104–107

Channel 1 2X Vector Phase measurement value

108–111

Channel 2 2X Vector Phase measurement value

112–115

Peak Speed measurement value

116–119

Channel 1 Gap measurement value

120–123

Channel 2 Gap measurement value