beautypg.com

Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual

Page 106

background image

Publication GMSI10-UM013D-EN-P - May 2010

96 Specifications

Inputs

2 Channels

Transducer Power

Voltage Range

Sensitivity

Input Impedance

Eddy current transducer signals
Accelerometer signals
Voltage signals from any dynamic
measurement device, such as a velocity or
pressure transducer

Constant voltage (+24V dc)*
Constant current (4.5 mA ± 20% from
+24V dc)*
None (voltage input)

*Tachometer may be powered, constant voltage,

or configured as voltage input.

Selectable in software as 0 to ±20 V (min)
40 V max. peak-to-peak

User configurable in software

Greater than 100 kohms

Tachometer

1 Tachometer Input

Input Impedance

Speed/Frequency Range

Speed Measurement Error

±25 V (50 V max. peak to peak)
1 to 50,000 events per revolution

120 kohms minimum

1 to 1,200,000 RPM
0.0167 to 20,000 Hz

1 to 12,000 RPM* +/- 1 RPM
12,001 to 120,000 RPM* +/- 6 RPM
120,001 to 1,200,000 RPM* +/- 50 RPM

* Exponential Averaging Time Constant

parameter set to

120ms

Outputs

4-20 mA Outputs

Buffered Outputs

Each output is independently programmed
to represent any measured parameter, from
either channel.
Two isolated outputs
300 ohm max load

1 active buffer per vibration input channel
Resistive buffer for tachometer

Indicators

7 LEDs Module Status - red/green

Network Status - red/green
Channel 1 Status - yellow/red
Channel 2 Status - yellow/red
Tachometer Status - yellow/red
Setpoint Multiplier -yellow
Relay - red

XM-122 Technical Specifications

Product Feature

Specification