Mounting the module – Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual
Page 58
Publication GMSI10-UM013D-EN-P - May 2010
48 Installing the XM-122 gSE Vibration Module
XM Serial Configuration Utility or RSNetWorx™ for DeviceNet™ (Version
3.0 or later) to set the network node address. Refer to the appropriate
documentation for details.
Mounting the Module
The XM-122 mounts on the XM-940 terminal base unit, Cat. No. 1440-TB-A.
We recommend that you mount the module after you have connected the
wiring on the terminal base unit.
IMPORTANT
The baud rate for the XM-122 is set by way of "baud
detection" (Autobaud) at power-up.
ATTENTION
The XM-122 module is compatible only with the XM-940
terminal base unit. The keyswitch on the terminal base unit
should be at position 1 for the module.
Do not attempt to install XM-122 modules on other
terminal base units.
Do not change the position of the keyswitch after
wiring the terminal base.
ATTENTION
This module is designed so you can remove and insert it
under power. However, when you remove or insert the
module with power applied, I/O attached to the module
can change states due to its input/output signal changing
conditions. Take special care when using this feature.
WARNING
When you insert or remove the module while power is on,
an electrical arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is
removed or the area is nonhazardous before proceeding.
IMPORTANT
Install the overlay slide label to protect serial connector and
electronics when the serial port is not in use.